Preset speed operation – Toshiba Tosvert VF-AS1 User Manual
Page 74
E6581301
E-8
5
+
The functions assigned to the following control input terminals (contact input:
⇒ Refer to Section 7.2) are always
activated regardless of the settings of the command mode selection EOQF and frequency setting mode selection 1
HOQF
.
• Reset terminal (default setting: RES, valid only for tripping)
• Standby terminal (assigned to ST by default)
• Emergency stop terminal
+
To make changes in the command mode selection EOQF and the frequency setting mode selection 1 HOQF first
stop the inverter temporarily.
No change can be made to them if the inverter is in operation.
■
Preset speed operation
EOQF
: Set this parameter at (terminal board).
HOQF
: Any setting is valid.
1) Setting the run, stop and operation frequencies with the operation panel
Title
Function
Example of setting
EOQF
Command mode selection
(Operation
panel input)
HOQF
Frequency setting mode
selection 1
(Operation
panel input)
Run/stop :Press the and keys
on the operation panel
+
To switch between forward run and reverse run,
use the forward/reverse run selection HT.
Speed command :Press the and
keys on the operation
panel to set the frequency.
Motor
IM
CCA
F
R
ST
R/L1
CC
Shorted by a shorting bar when
shipped from the factory.
Power
supply
S/L2
T/L3
U/T1
V/T2
W/T3
RX VI/II RR/S4 PP
To save the frequency,
press the ENT key. Then,
HE
and the set frequency
are displayed alternately for
a while.
Inverter
RUN
STOP