beautypg.com

Selection of wiring equipment, E6581300 j-2 – Toshiba Tosvert VF-AS1 User Manual

Page 232

background image

E6581300

J-2

10

Selection of wiring equipment

No-fuse breaker (MCCB)

Magnetic contactor

(MC)

Input current[A]

Without Reactor

With Reactor

Without
Reactor

With

Reactor

Voltage

class

Applicable

motor [kW]

Inverter model

Without

Reactor

With

Reactor

Rated

current

[A]

Type

form

(*1)

Rated

current

[A]

Type

form

(*1)

Type

form

(*1)

Type

form

(*1)

0.4

VFAS1-2004PL

3.5

2.1

6.3

GV2 L10

4

GV2 L08

LC1D096

LC1D096

0.75

VFAS1-2007PL

6.1

3.2

10

GV2 L14

6.3

GV2 L10

LC1D096

LC1D096

1.5

VFAS1-2015PL

11.5

6.4

18

GV2 L20

10

GV2 L14

LC1D096

LC1D096

2.2

VFAS1-2022PL

15

9.3

25

GV2 L22

14

GV2 L16

LC1D096

LC1D096

3.7/4.0

VFAS1-2037PL

26.0

15.5

32

GV2 L32

25

GV2 L22

LC1D126

LC1D096

5.5

VFAS1-2055PL

35

22. 5

50

NJ50EB

32

GV2 L32

LC1D126

LC1D126

7.5

VFAS1-2075PL

45

34.5

60

NJ100FB

40

NJ50EB

LC1D326

LC1D256

11

VFAS1-2110PM

-

53.5

-

-

75

NJ100FB

-

LC1D506

15

VFAS1-2150PM

-

72

-

-

100

NJ100FB

-

LC1D506

18.5

VFAS1-2185PM

-

77

-

-

100

NJ100FB

-

LC1D506

22

VFAS1-2220PM

-

88

-

-

125

NJ225FB

-

LC1D806

30

VFAS1-2300PM

-

125

-

-

150

NJ225FB

-

LC1D806

37

VFAS1-2370PM

-

140

-

-

175

NJ225FB

-

LC1D115J

45

VFAS1-2450PM

-

165

-

-

200

NJ225FB

-

LC1D150J

55

VFAS1-2550P

-

200

-

-

250

NJ400F

-

LC1F185J

200V
class

75

VFAS1-2750P

-

270

-

-

350

NJ400F

-

LC1F265J

0.75

VFAS1-4007PL

3.7

2.1

5

GV2 L10

4

GV2 L08

LC1D096

LC1D096

1.5

VFAS1-4015PL

5.8

3.8

10

GV2 L14

6.3

GV2 L10

LC1D096

LC1D096

2.2

VFAS1-4022PL

8.2

5.7

14

GV2 L16

10

GV2 L14

LC1D096

LC1D096

3.7/4.0

VFAS1-4037PL

14.0

8.7

18

GV2 L20

14

GV2 L16

LC1D096

LC1D096

5.5

VFAS1-4055PL

20.5

12.7

32

GV2 L32

25

GV2 L22

LC1D126

LC1D126

7.5

VFAS1-4075PL

27

16.3

32

GV2 L32

25

GV2 L22

LC1D186

LC1D186

11

VFAS1-4110PL

36.5

21.5

50

NJ50EB

30

NJ30E

LC1D256

LC1D186

15

VFAS1-4150PL

48

33.5

60

NJ100FB

40

NJ50EB

LC1D326

LC1D256

18.5

VFAS1-4185PL

-

45.5

-

-

60

NJ100FB

-

LC1D326

22

VFAS1-4220PL

-

50

-

-

60

NJ100FB

-

LC1D326

30

VFAS1-4300PL

-

66

-

-

100

NJ100FB

-

LC1D506

37

VFAS1-4370PL

-

84

-

-

100

NJ100FB

-

LC1D806

45

VFAS1-4450PL

-

105

-

-

125

NJ225FB

-

LC1D806

55

VFAS1-4550PL

-

120

-

-

150

NJ225FB

-

LC1D806

75

VFAS1-4750PL

-

165

-

-

200

NJ225FB

-

LC1D115J

90

VFAS1-4900PC

-

170

-

-

200

NJ225FB

-

LC1D150J

110

VFAS1-4110KPC

-

200

-

-

250

NJ400F

-

LC1D185J

132

VFAS1-4132KPC

-

240

-

-

300

NJ400F

-

LC1D225J

160

VFAS1-4160KPC

-

290

-

-

350

NJ400F

-

LC1D265J

200

VFAS1-4200KPC

-

360

-

-

500

NJ600F

-

LC1D400J

220

VFAS1-4220KPC

-

395

-

-

500

NJ600F

-

LC1D400J

280

VFAS1-4280KPC

-

495

-

-

600

NJ600F

-

LC1D500J

355

VFAS1-4355KPC

400

VFAS1-4400KPC

400V
class

500

VFAS1-4500KPC

(*1): Type forms of Toshiba Schneider Electric Ltd. products.
(*2): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
(*3): Choose the MCCB according to the power supply capacity.

For comply with UL and CSA standard, use the fuse certified by UL and CSA.

(*4): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current for

the motor rated current.

(*5): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*6): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability of

the contact by using 2a-type contacts in parallel connection.