Selection of wiring equipment, E6581300 j-2 – Toshiba Tosvert VF-AS1 User Manual
Page 232
E6581300
J-2
10
■
Selection of wiring equipment
No-fuse breaker (MCCB)
Magnetic contactor
(MC)
Input current[A]
Without Reactor
With Reactor
Without
Reactor
With
Reactor
Voltage
class
Applicable
motor [kW]
Inverter model
Without
Reactor
With
Reactor
Rated
current
[A]
Type
form
(*1)
Rated
current
[A]
Type
form
(*1)
Type
form
(*1)
Type
form
(*1)
0.4
VFAS1-2004PL
3.5
2.1
6.3
GV2 L10
4
GV2 L08
LC1D096
LC1D096
0.75
VFAS1-2007PL
6.1
3.2
10
GV2 L14
6.3
GV2 L10
LC1D096
LC1D096
1.5
VFAS1-2015PL
11.5
6.4
18
GV2 L20
10
GV2 L14
LC1D096
LC1D096
2.2
VFAS1-2022PL
15
9.3
25
GV2 L22
14
GV2 L16
LC1D096
LC1D096
3.7/4.0
VFAS1-2037PL
26.0
15.5
32
GV2 L32
25
GV2 L22
LC1D126
LC1D096
5.5
VFAS1-2055PL
35
22. 5
50
NJ50EB
32
GV2 L32
LC1D126
LC1D126
7.5
VFAS1-2075PL
45
34.5
60
NJ100FB
40
NJ50EB
LC1D326
LC1D256
11
VFAS1-2110PM
-
53.5
-
-
75
NJ100FB
-
LC1D506
15
VFAS1-2150PM
-
72
-
-
100
NJ100FB
-
LC1D506
18.5
VFAS1-2185PM
-
77
-
-
100
NJ100FB
-
LC1D506
22
VFAS1-2220PM
-
88
-
-
125
NJ225FB
-
LC1D806
30
VFAS1-2300PM
-
125
-
-
150
NJ225FB
-
LC1D806
37
VFAS1-2370PM
-
140
-
-
175
NJ225FB
-
LC1D115J
45
VFAS1-2450PM
-
165
-
-
200
NJ225FB
-
LC1D150J
55
VFAS1-2550P
-
200
-
-
250
NJ400F
-
LC1F185J
200V
class
75
VFAS1-2750P
-
270
-
-
350
NJ400F
-
LC1F265J
0.75
VFAS1-4007PL
3.7
2.1
5
GV2 L10
4
GV2 L08
LC1D096
LC1D096
1.5
VFAS1-4015PL
5.8
3.8
10
GV2 L14
6.3
GV2 L10
LC1D096
LC1D096
2.2
VFAS1-4022PL
8.2
5.7
14
GV2 L16
10
GV2 L14
LC1D096
LC1D096
3.7/4.0
VFAS1-4037PL
14.0
8.7
18
GV2 L20
14
GV2 L16
LC1D096
LC1D096
5.5
VFAS1-4055PL
20.5
12.7
32
GV2 L32
25
GV2 L22
LC1D126
LC1D126
7.5
VFAS1-4075PL
27
16.3
32
GV2 L32
25
GV2 L22
LC1D186
LC1D186
11
VFAS1-4110PL
36.5
21.5
50
NJ50EB
30
NJ30E
LC1D256
LC1D186
15
VFAS1-4150PL
48
33.5
60
NJ100FB
40
NJ50EB
LC1D326
LC1D256
18.5
VFAS1-4185PL
-
45.5
-
-
60
NJ100FB
-
LC1D326
22
VFAS1-4220PL
-
50
-
-
60
NJ100FB
-
LC1D326
30
VFAS1-4300PL
-
66
-
-
100
NJ100FB
-
LC1D506
37
VFAS1-4370PL
-
84
-
-
100
NJ100FB
-
LC1D806
45
VFAS1-4450PL
-
105
-
-
125
NJ225FB
-
LC1D806
55
VFAS1-4550PL
-
120
-
-
150
NJ225FB
-
LC1D806
75
VFAS1-4750PL
-
165
-
-
200
NJ225FB
-
LC1D115J
90
VFAS1-4900PC
-
170
-
-
200
NJ225FB
-
LC1D150J
110
VFAS1-4110KPC
-
200
-
-
250
NJ400F
-
LC1D185J
132
VFAS1-4132KPC
-
240
-
-
300
NJ400F
-
LC1D225J
160
VFAS1-4160KPC
-
290
-
-
350
NJ400F
-
LC1D265J
200
VFAS1-4200KPC
-
360
-
-
500
NJ600F
-
LC1D400J
220
VFAS1-4220KPC
-
395
-
-
500
NJ600F
-
LC1D400J
280
VFAS1-4280KPC
-
495
-
-
600
NJ600F
-
LC1D500J
355
VFAS1-4355KPC
400
VFAS1-4400KPC
400V
class
500
VFAS1-4500KPC
(*1): Type forms of Toshiba Schneider Electric Ltd. products.
(*2): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
(*3): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*4): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current for
the motor rated current.
(*5): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*6): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability of
the contact by using 2a-type contacts in parallel connection.