F-7

6

Connection method

1) a-contact input

CC

Input
terminal

+This function is activated when the input terminal and CC

(common) are short-circuited. Use this function to
specify forward/reverse run or a preset speed operation.

Inverter

a-contact switch

Sink setting

2) Connection with transistor output

+

Operation can be controlled by connecting the input and CC

(common) terminals to the output (no-contacts switch) of the
programmable controller. Use this function to specify
forward/reverse run or a preset speed operation. Use a
transistor that operates at 24Vdc/5mA.

CC

Input
terminal

Inverter

Programmable controller

* Interface between programmable controller and inverter

Note:

When using a programmable controller with open collector outputs for control, connect it to the P24/PLC
terminal, as shown in the figure below, to prevent the inverter from malfunctioning because of current
flowing in.

Also, be sure to turn the SW1 slide switch to the PLC position.

Programmable controller

PLC

+24V
power
supply

PLC

SW1

+24V

F~S4

CC

P24/PLC

Inverter

3) Sink logic/source logic input

Sink logic/source logic (input/output terminal logic) switching is possible.
⇒ For details, refer to Section 2.3.2.