Input terminal information
Input terminal 1 (F)
: F111 : 0
Input terminal 2 (R)
: F112 : 1
When there is signal input
Input terminal 3 (ST)
: F113 : 2
Input terminal 4 (RES)
: F 114 : 3
When there is no signal input
Input terminal 5 (S1)
: F115 : 4
(blank in the upper half)
Input terminal 6 (S2)
: F116 : 5
Input terminal 7 (S3)
: F117 : 6
Input terminal 8 (RR/S4) : F118 : 7
Data bit of communication
No. FE06
Input terminal 9 (LI1)
: F119 : 8
When there is signal input
Input terminal 10 (LI2)
: F120 : 9
Input terminal 11 (LI3)
: F121 : 10
When there is no signal input
Input terminal 12 (LI4)
: F122 : 11
(blank in the upper half)
Input terminal 13 (LI5)
: F123: 12
When there is signal input
Input terminal 14 (LI6)
: F124: 13
Input terminal 15 (LI7)
: F125: 14
When there is no signal input
Input terminal 16 (LI8)
:F126: 15
(blank in the upper half)
Input terminal 9 to 16
: Expansion terminal board option unit
A
dd-on opt
ion
C
D
Note: When H is set at a number of to expansion terminal board option input terminal information (C, D)
indicate information of lower 8 bit terminal (B0~B7).
■
Output terminal information
Output terminal 1 (OUT1) : F130 : 1
When there is signal output
Output terminal 2 (OUT2) : F131 : 2
Output terminal 3 (FL)
: F132 : 3
When there is no signal output
(blank in the upper half)
Data bit of communication
No. FE 07
Output terminal 4 (OUT3) : F133 : 4
Output terminal 5 (OUT4) : F134 : 5
Output terminal 6 (R1)
: F135 : 6
When there is signal output
Output terminal 7 (OUT5) : F136 : 7
Output terminal 8 (OUT6) : F137 : 8
When there is no signal output
Output terminal 9 (R2)
: F138 : 9
(blank in the upper half)
Output terminal 10 (R3)
: F168 : 10
Output terminal 11 (R4)
: F169 : 11
Output terminal 4, 5, 6 (OUT3, OUT4, R1) :Expansion terminal board
option unit 1
Output terminal 7, 8, 9 (OUT5, OUT6, R2) :Expansion terminal board
option unit 2
Output terminal 10, 11 (R3, R4)
:16-bit BIN/BCD option
A
d
d-on opti
on
■
Cumulative operation time
For indication of cumulative operation hours, running hours are counted up when the output frequency monitor
reads a frequency other than 0.0Hz. 10 hours is indicated as 0.1 (unit of Indication).