7

Table of setting of contact input terminal function

Parameter setting

Parameter setting

Positive

logic

Negative

logic

Function

Positive

logic

Negative

logic

Function

No function is assigned

Servo lock signal

F: Forward run command

Simple positioning (positioning loop)

R: Reverse run command

Integrating wattmeter display clear

ST: Standby

Trace back trigger signal

RES: Reset

Light-load high-speed operation
prohibitive signal

S1: Preset speed 1

No function assigned

S2: Preset speed 2

No function assigned

S3: Preset speed 3

No function assigned

S4: Preset speed 4

Binary data write

Jog run

Up/down frequency (up)

*1

Emergency stop

Up/down frequency (down)

*1

DC braking

Up/down frequency (clear)

Acceleration/deceleration switching 1

No function assigned

Acceleration/deceleration switching 2

No function assigned

V/f switching signal 1

Forward/reverse selection

V/f switching signal 2

Run/stop command

*3

Torque limit switching signal 1

Commercial power/INV switching

Torque limit switching signal 2

Frequency reference priority switching

PID control OFF selection

VI/II terminal priority

Pattern operation group 1

Command terminal board priority

Pattern operation selection 2

Permission of parameter editing

Pattern operation continuation signal

Control switching (speed/torque)

Pattern operation trigger signal

No function assigned

External thermal error

No function assigned

Forced switching from communication to local

No function assigned

HD operation retention

No function assigned

PID differentiation/integration clear

Rapidest deceleration command

PID forward/reverse switching

Preliminary excitation

*4

Forced continuous operation

Braking request

Specified speed operation

No function assigned

Acceleration/deceleration suspend
signal

Brake answer back input

Power failure synchronized signal

No function assigned

My function RUN signal

Traverse permission signal

Auto-tuning signal

Speed gain switching

*1: Valid when HOQF(Frequency setting mode selection 1) is set at (Up/down frequency).

The frequency setting range is between =~WN(Upper limit frequency). The acceleration/deceleration time
with respect to the frequency setting remains CEE/FGE, unless switching between acceleration and
deceleration is performed.

*2: To switch acceleration/deceleration pattern, V/f pattern, torque limit 1~4, give the following signals to switching

functions.

*3: If , (F: Forward run command) or , (R: Reverse run command) is assigned at the same time, this

function has a priority.

*4: After the motor slows down and comes to a full stop at a pre-excitation command, the motor is set free

momentarily to bring it into a pre-excitation state.
This function should not be used when H is set to or 4. Or the inverter might malfunction.

Switching signal 1

Switching signal 2

Acceleration/deceleration, V/f, torque limit 1

OFF

OFF

Acceleration/deceleration, V/f, torque limit 2

ON

OFF

Acceleration/deceleration, V/f, torque limit 3

OFF

ON

Acceleration/deceleration, V/f, torque limit 4

ON

ON