E6581301

F-35

6

*1

Stop position
control mode

Run command (F)

Preset speed 1 (S1)

Preset speed 2 (S2)

Stop position command signal (RR/S4)

Preset-speed operation frequency 1

Preset speed operation frequency 2

0

Time [s]

Output frequency [Hz]

H
Positioning completion range

*1

Preset speed
operation frequency 2

If the stop position control command is entered during high-speed operation, a trip may occur because of
overcurrent or overvoltage. To avoid this, do not enter the stop position control command before the motor
enters into low-speed operation.

If a trip occurs because of overvoltage when stop position control is performed

If a trip due to overvoltage (OP2 or OP3) occurs when the motor is decelerated by stop position control, reduce the
proportional (P) gain with H to prolong the deceleration time.
Note:The deceleration time setting (FGE) has no effect during stop position control.

Proportional (P) gain (H)

During deceleration
Overvoltage trip
(QR or QR)

Time [s]

Output frequency [Hz]

Time [s]

Output frequency [Hz]

Acceleration

Deceleration

Acceleration