beautypg.com

Alarm system – Grass Valley Trinix NXT v.3.3.1 User Manual

Page 67

background image

Trinix NXT — Installation and Service Manual

67

Trinix Frames

Alarm System

The operation of cooling fans, frame power supplies, on-board power sup-
plies, and primary vs. secondary Broadlinx boards are all monitored. Any
alarm for these critical items is treated as a Primary alarm. With the release
of Broadlinx 3.1, the router’s system alarm has two modes, “No alarms”
and “Primary alarm.” All alarms (multiple fan failure, power supply
failure, etc.) are considered Primary alarms. All major components include
a local alarm LED.

The master alarm indicator is on the front panel (Power/Alarm) where
green indicates normal operation and red indicates a Primary alarm.

Symmetrical Frame

The rear panel Alarm BNC is configured to report primary alarms only. The
TRX-NXT-128x128 and TRX-NXT-256x256 is configured via jumper on the
NR/SR-33000 board. The location of the board is shown in

Figure 63 on

page 136

and

Figure 65 on page 138

. The TRX-NXT-512x512 is configured

via a jumper on the RP-33500 512 x 512 Rear Panel board as shown on

Figure 68 on page 141

.

The Alarm BNC for the TRX-NXT-256x512 version is configured the same
as the TRX-NXT-128x128 or TRX-NXT-256x256. In other words, through
the jumper on the NR-33000 board. See

Figure 28

.

Note

Secondary alarms are no longer supported.

Fan and Power Supply alarm status is concentrated on the SC board and is
reported through the OPM board for the Asymmetrical frames. The Power
Supply alarms are configured with the dual in-line package (DIP) switches
on the SC boards. (See Configuration DIP Switches

on page 231

)

Figure 28. Rear Panel Master Alarm Circuit (left) and Example Of Customer-supplied Indicator
Circuit (right)

.

EXTERNAL CIRCUIT

(EXAMPLE)

NOT TO EXCEED

24 VDC @ 20 mA

REAR PANEL BNC

This manual is related to the following products: