Grass Valley Trinix NXT v.3.3.1 User Manual
Page 351

Trinix NXT — Installation and Service Manual
351
Protected Paths Overview
When adding an HO33120 or HO33300 output board to the Trinix router 
used in a Protected Path, the following should be observed:
•
Add the board during a non-critical time as it may take up to four 
seconds to recognize the board. A two-minute delay can cause signal 
disruption on the active board’s outputs.
•
Telnet into the control system and turn off the refresh feature; wait 30 
seconds before turning on the refresh feature once the output board is 
powered up.
How the refresh feature is turned off depends on the installed control 
system. 
Control System Refresh Command
To turn refresh off on the AccuSwitch control system:
CM1_M(A)-> refreshStop
value = 1 = 0x1
To restart refresh on the AccuSwitch control system:
CM1_M(A)-> refreshStart
value = 0 = 0x0
CM1_M(A)->
To turn refresh off on a Jupiter Express system suspend the refresh task:
SB > ts rfxp
value = 0 = 0x0
To restart refresh on a Jupiter Express system suspend the refresh task:
SB > tr rfxp
value = 0 = 0x0
SB >
For more information, contact Grass Valley’s Technical support (See Con-
tacting Grass Valley
).