Trinix NXT — Installation and Service Manual
219
SMS 7000 / Encore Control
SMS 7000 / Encore Control
These control systems use an Ethernet connection to the Broadlinx option
(NR-33000 Sync/NIC/OPM board).
1.
Set the Trinix INT XPT CNTL rear-panel DIP switch to On (switch
closed). See
.
Figure 129.
In the internal-Crosspoint bus control mode, the Broadlinx board sends
commands to the Crosspoint bus.
2.
Set Level switches:
Two back-panel rotary switches are used to set the level address of the
router. The rear-panel rotary Level switch must be set to Ultra-Cros-
spoint bus, Level 1; that is, the Super/Ultra rotary switch must be
pointed straight down to “0” and the adjacent rotary switch must point
at “1.”
Note
On all the Trinix rotary switches, use the triangular arrowhead for pointing
(not the screwdriver slot).