API

Command Reference A-9

Command

Syntax

Description

Obank1,

bank2,
bank3,
bank4

Set any of the 32 digital outputs (separated into four 8-bit

banks) to a specified setting, where

bankn

(

n

=

1

,

2

,

3

,

4

)

is an argument in the form of the number

nnn

such that

000

<

nnn

<

255

when converted to binary format

represents the desired settings for the 8-bit bank.

O

Set Digital Outputs

O?

Query current state of digital output.

Pstart,

stop

Set the Trigger and/or Stop times for an acquisition configured

for start and/or stop on absolute time, where

start

and

stop

are in the standard Time/Date input format:

hh:mm:ss:t,MM/DD/YY

where

hh

is in hours,

mm

is in

minutes,

ss

is in seconds,

t

is in tenths of a second,

MM

is

the month,

DD

is the day, and

YY

is the year.

P

Program Trigger Times

P?

Query current start and stop times.

Qresp,

hll,
scan,
block,
sep

Set the query terminators with the following parameters:

resp

is the response terminator,

hll

is the channel terminator,

scan

is the scan terminator, and

block

is the Trigger

Block terminator.

sep

is the separator terminator which determines whether or

not a separator character should be used. Valid options for

sep

are:

0

- Place no separators in returned buffered scan

data when it is read, and

1

- Place a separator whose value

is determined by the current Set User Terminator (

V

)

command setting into the returned buffer data when it is
read.

Q

Set Query Terminator

Q?

Query current terminator settings.

QC?

Query Card Data

QC?

Read back the card identification and calibration information

from the scanning card previously selected by the Select
Card
(

C#

) command.

Rtype

Read scan data from the Acquisition Buffer where

type

is the

type of data request being made. Valid options for

type

are:

1

- Read the oldest scan currently residing in the

Acquisition Buffer,

2

- Read the oldest complete Trigger

Block currently residing in the Acquisition Buffer, and

3

-

Read all the scan data that currently resides in the
Acquisition Buffer.

R

Read Buffered Data

R?

Query the contents of the Acquisition Buffer.

R#

Read Last Readings

R#chans

Queries the last readings from the HLL Registers for specified

channels.

chans

may be in two forms:

chan

(for a single channel

where

1

<

chan

<

max

) or

first-last

(for a range of

channels where

1

<

first

<

last

<

max

), where

max

=

992

for the TempScan/1100 and

max

=

744

for the

MultiScan/1200.

Stime

Set the internal real-time clock where

time

is in the standard

Time/Date input format:

hh:mm:ss:t, MM/DD/YY

where

hh

is in hours,

mm

is in minutes,

ss

is in seconds,

t

is in tenths of a second,

MM

is the month,

DD

is the day, and

YY

is the year.

S

Set Real-Time Clocks

S?

Query the internal real-time clock.

Tstart,

stop,
re-arm,
sync

Configure an acquisition of scan data with the following

parameters:

start

is the start event and

stop

is the stop event

re-arm

determines if the unit should continue acquiring after

the first acquisition completes, where

1

is on and

0

is off.

sync

determines if acquisition events should be synchronized

with the internal timebases, where

1

is on and

0

is off.

T

Set Trigger

Configuration

T?

Query the present trigger configuration