Table 101 – Basler Electric DGC-2020HD User Manual
Page 399

9469300990 Rev B
389
SPN
FMI
String Displayed
Description
523566
#
INJECTN PERIOD CYL 6
Caption String for Single Cylinder Injection Period
523567
#
INJECTN PERIOD CYL 7
Caption String for Single Cylinder Injection Period
523568
#
INJECTN PERIOD CYL 8
Caption String for Single Cylinder Injection Period
523600
#
ECU ERROR
String for Diagnostic Trouble Code Indicating ECU Error
523601
#
ECU ERROR
String for Diagnostic Trouble Code Indicating ECU Error
523602
#
FAN SPEED
Caption String for Engine Fan Speed
523604
#
RXENGTMP CAN MSG
Caption String for CANBus Message
523605
#
TSC1-AE MSG MISSING
Caption String for CANBus Message
523606
#
TSC1-AR MSG MISSING
Caption String for CANBus Message
523607
#
TSC1-DE MSG MISSING
Caption String for CANBus Message
523608
#
TSC1-DR MSG MISSING
Caption String for CANBus Message
523609
#
TSC1-PE MSG MISSING
Caption String for CANBus Message
523610
#
TSC1-VE MSG MISSING
Caption String for CANBus Message
523611
#
TSC1-VR MSG MISSING
Caption String for CANBus Message
523612
#
ECU ERROR
String for Diagnostic Trouble Code Indicating ECU Error
523613
#
RAIL PRESSURE
Caption String for Rail Pressure
523615
#
METERING UNIT VALVE
Caption String for Metering Unit Valve
523617
#
ECU ERROR
String for Diagnostic Trouble Code Indicating ECU Error
Table 101. DTCs Displayed by the DGC-2020HD (FMI Strings)
FMI
String Displayed
Description
0
DATA HI MOST SEVERE
Data is higher than expected at the most severe level
1
DATA LO MOST SEVERE
Data is lower than expected at the most severe level
2
DATA ERRATIC OR BAD
Data is erratic, intermittent, or incorrect
3
VOLTS HI OR SHORTED
Measured voltage is higher than expected or shorted to a high source
4
VOLTS LO OR SHORTED
Measured voltage is lower than expected or shorted to a low source
5
CURRENT LO OR OPEN
Measured current is lower than expected or the circuit is open
6
CURRENT HI OR SHORTED
Measured current is higher than expected or shorted
7
MECHANICAL SYSTM ERR
Mechanical system error
8
FREQ OR PWM ERROR
Error in frequency, pulse width or period of any frequency or PWM signal
is outside its predetermined limits
9
ABNORMAL UPDATE RATE
Update rate of parameter is abnormal
10
DATA RT OF CHG ERR
Rate of change of data is abnormal
11
FAILURE CAUSE UNKNOWN
String indicating failure cause is unknown
12
BAD INTELLIGNT DEVICE
Engine ECU is reporting that an intelligent device or component failure
has been detected
13
OUT OF CALIBRATION
Device or parameter is out of calibration
14
CONSULT ENG MFG DATA
User should consult engine manufacturer's data
15
DATA HI LST SEVERE
Data is higher than expected at the least severe level
16
DATA HI MODERATE SVR
Data is higher than expected at a moderately severe level
17
DATA LO LST SEVERE
Data is lower than expected at the least severe level
18
DATA LO MODERATE SVR
Data is lower than expected at a moderately severe level
19
NETWORK DATA ERR
String Indicating Network Data contained an error indication
DGC-2020HD