Basler Electric DGC-2020HD User Manual
Page 276
![background image](https://www.manualsdir.com/files/773949/content/doc276.png)
266
9469300990 Rev B
Figure 169. Floating Rated Data Screen
Table 77. Settings for Rated Data
Locator
Setting
Range
Increment
Unit
A
Current Sensing Input Type
5 A CTs or 1A CTs
n/a
n/a
B
Rated Frequency of the Unit
50 Hz or 60 Hz
n/a
n/a
C
Alternate Frequency
10 to 90
0.01
Hz
D
Rated Engine RPM
750 to 3,600
1
RPM
E
PT – Primary Volts
1 to 500,000
1
volts
F
PT – Secondary Volts
1 to 600
1
volts
G
CT – Primary Amps
1 to 99,999
1
amperes
H
Low-line Scale Factor
0.001 to 3
0.001
n/a
I
Rated Volts
1 to 500,000
1
volts
J
Rated Power Factor
–1 to 1
0.01
n/a
K
Rated kW
0 to 1,000,000
0.01
kW
L
Phase Rotation
ABC or ACB
n/a
n/a
M
Voltage Sensing
Delta, Wye, 1 Phase A-B, 1
Phase A-C, Grounded Delta
n/a
n/a
N
CT Phase Connection
A, B, C, AB, BC, CA, or
CT ABC
n/a
n/a
Configuration
DGC-2020HD