9469300990 Rev B
211
Name
Description
Symbol
Silence
True while the Silence front panel button is
pressed.
Up
True while the Up front panel button is
pressed.
Generator Protection
Frequency
True when the 81-x element is tripped.
Loss of
Excitation
True when the 40Q-x element is tripped.
Overcurrent
True when the 51-x element is tripped.
Overvoltage
True when the 59-x element is tripped.
Phase
Imbalance
True when the 47-x element is tripped.
Power
True when the 32-x element is tripped.
Undervoltage
True when the 27-x element is tripped.
Vector Shift
True when the 78-x element is tripped.
Generator States
In Alarm State
True when the DGC-2020HD is in the
alarm state.
In Connecting
State
True when the DGC-2020HD is in the
connecting state.
In Cooling State
True when the DGC-2020HD is in the
cooling state.
In Cranking
State
True when the DGC-2020HD is in the
cranking state.
In Disconnect
State
True when the DGC-2020HD is in the
disconnect state.
In Prestart State
True when the DGC-2020HD is in the pre-
start state.
In Pulsing State
True when the DGC-2020HD is in the
pulsing state.
In Ready State
True when the DGC-2020HD is in the
ready state.
In Resting State
True when the DGC-2020HD is in the
resting state.
DGC-2020HD
BESTlogic
™Plus