Basler Electric DGC-2020HD User Manual
Page 217

9469300990 Rev B
207
Name
Description
Symbol
Audible Horn
True when the Audible Horn is active.
Auto Mode
True when the DGC-2020HD is in Auto
Mode or the Auto Mode logic element is
true.
Auto Restart
True when the Automatic Restart function
is active.
AVR Output Out
of Range
True when the AVR Output Limit settings
have been exceeded.
Battery Charger
Fail
True when the Battery Charger Fail input is
true, the Alarm Type is set to Status Only,
and the activation delay has expired.
Battle Override
True when the Battle Override input is true.
Bus x Dead
True when the Bus x Dead condition
settings have been exceeded.
Bus x Fail
True when the Bus Fail condition settings
have been exceeded.
Bus x Forward
Rotation Status
True when the bus rotation matches the
Phase Rotation setting.
Bus x Reverse
Rotation
True when the bus rotation is opposite of
the Phase Rotation setting.
Bus x Stable
True when the Bus Stable condition
settings have been exceeded.
CAN bus Error
Passive
True when a passive error is annunciated
by the CAN bus.
CAN bus Off
True when the CAN bus is off.
Cool Down
Timer Active
True when the Cool Down Timer is timing
out. The Cool Down Timer is true under
two circumstances:
1. The unit is in Auto mode and ATS is
removed, causing the DGC-2020HD to go
into a cool down state.
2. The engine is running (in Run or Auto
mode with ATS applied) and the load has
been removed (i.e. the EPSSUPLOAD
status input is false due to small load). If
the load is reapplied, the Cool Down Timer
stops and resets, and it will restart when
the load is removed the next time.
Emergency
Stop
True when the Emergency Stop button has
been pressed.
Engine Running
True while the engine is running.
EPS Supplying
Load
True when the EPS threshold has been
exceeded and the EPS is supplying load.
DGC-2020HD
BESTlogic
™Plus