Run Statistics
BESTCOMSPlus Navigation Path: Metering Explorer, Run Statistics
Front Panel Navigation Path: Metering > Run Statistics
This screen provides Cumulative Run Statistics, Session Run Statistics, and Commission Date. See
Figure 96.
The Cumulative Run Statistics are tracked from the first time the genset was started. The Session Run
Statistics are tracked from the last time the genset was started until the following shutdown.
The Commission Date, Number of Starts, Hours Until Maintenance, Total kWh, Total Engine Run Time,
Loaded Run Time, and Unloaded Run time can be changed by clicking the Edit Cumulative Run Statistics
button. This is helpful when installing the DGC-2020HD into a pre-existing system. This allows the current
statistics of the genset to be transferred into the DGC-2020HD for uninterrupted tracking.
The Hours Until Maintenance pre-alarm is configured on the Pre-Alarms screen in the Settings Explorer.
The Hours Until Maintenance field displays “OFF” when the Maintenance Interval pre-alarm is disabled.
Clicking Reset Maintenance Interval resets the Hours Until Maintenance to the value set for the
Maintenance Interval pre-alarm on the Pre-Alarms screen in the Settings Explorer.
Figure 96. Metering Explorer, Run Statistics Screen
Synchronization
BESTCOMSPlus Navigation Path: Metering Explorer, Synchronization
Front Panel Navigation Path: Metering > Synchronization
Slip frequency, slip angle, and the voltage difference between the current synchronization source and
destination are displayed on the Synchronization screen. The Synchronization screen is automatically
displayed on the front panel while the synchronizer is active. See Figure 97.
Figure 97. Metering Explorer, Synchronization Screen
DGC-2020HD
Metering