Name

Description

Symbol

GOV

Can be connected to inputs of other logic blocks. When the
governor is being raised, the Raise output is true. When being
lowered, the Lower output is true.

Idle Request

When the Set input is true, the DGC-2020HD sends an idle
request to the ECU on J1939 engines that are equipped to
receive such a request. The request consists of an enable bit
command and an idle RPM setting. At this time, only Volvo and
Cummins are implemented. ECUs that accept the idle RPM
setting set the engine to the requested RPM. ECUs that accept
only the enable bit command, set the engine to their internal idle
speed setting, ignoring the requested idle RPM from the DGC-
2020HD.

Lamp Test

The lamp test will be performed when the Set input is true. The
lamp test can also be accomplished by simultaneously pressing
the Up and Down buttons on the front panel of the DGC-
2020HD.

Load Take
Over

When the Set input is true, the generator is forced to start,
assume load, and disconnect from the mains, in an open
transition.

Logic Alarm

When the Set input is true, the DGC-2020HD goes into an alarm
condition.

Logic Pre-
Alarm

When the Set input is true, the DGC-2020HD goes into a Pre-
alarm condition.

Low Fuel Pre-
Alarm

When the Set input is true, a Low Fuel Pre-Alarm is annunciated
and the Low Fuel Level LED on the RDP-110 is illuminated.

Low Line
Override

When the Set input is true the 27, 59, 47, 51, 32, and 40Q
settings and the configurable element settings and are scaled by
the low-line scale factor setting.

DGC-2020HD

BESTlogic

Plus