Basler Electric DGC-2020HD User Manual
Page 385

9469300990 Rev B
375
Fault
Code
String
Description
506
AL LOW STARTER VOLTS
Battery voltage is too low for starting.
507
AL POM ERROR
A general POM error has been detected.
508
AL WRONG POM ID
POM sends a different identification number (ID) than expected.
509
AL CHECK POM FUSE
Check POM fuse.
510
AL OVERRIDE APPLIED
Override applied.
515
STARTER NOT ENGAGED
Starter of POM could not be engaged.
543
MULTIPLE FDH SLAVES
There is more than one device which is configured as Backup for
FDH-Functionality.
544
CONFIGURATION CHANGED
Gets active in case of changing system configuration e.g. by
changing ECU- or SAM-Device. Remains until undo procedure or
data is transferred by a valid maintenance case. Is cancelled
automatically.
549
AL PWR CUTOFF STR
This is the alarm from the function Emergency Stop Counter. ECU
power was disconnected while the engine was still running. This
could lead to a possible overpressure in the high pressure system
which might damage the engine.
555
AL CALL FIELD SERVICE
Gets active in case of completing a maintenance-case which
manipulates Engine-Parameters. Remains also after switching on-
off ECU until a valid release code is entered via Display- and
Button-Control of SAM-Device. Release Code is available via
Internet by a special procedure.
576
AL ESCM OVERRIDE STR
Exceeding of the corrected current MCR - odr DBR/MCR value.
594
AL L1 PRV 1 DEFECT STR
Yellow alarm pressure relief valve first rail.
595
AL L2 PRV 1 DEFECT STR
Red alarm pressure relief valve first rail.
598
AL L1 PRV 2 DEFECT STR
Yellow alarm pressure relief valve second rail.
599
AL L2 PRV 2 DEFECT STR
Red alarm pressure relief valve second rail.
610
AL WIRING SUCK RESTRCT 1
STR
Open load or short circuit on PWM HP fuel control block channel.
611
AL WIRING SUCK RESTRCT 2
STR
Open load or short circuit on PWM HP fuel control block channel 2.
612
AL WIRING PRESS CTRL VLV 1
STR
Open load or short circuit on PWM pressure regulating valve
channel.
613
AL WIRING PRESS CTRL VLV 2
STR
Open load or short circuit on PWM pressure regulating valve
channel 2.
615
AL EIL PROTECTION STR
Alarm for Protection Module in response to faulty or manipulated
EIL.
692
AL ECU PWR OFF ON REQ STR
ECU configuration changed, switch power off/on.
696
AL SMARTCONCT USB ERR
STR
Alarm configuration parameter.
697
AL SMARTCONCT RS485 ERR
STR
Alarm configuration parameter.
698
AL SD STOP BUTTON STR
Channel signals open load or internal error.
700
AL SD START BUTTON STR
Channel signals open load.
701
AL SD UP BUTTON STR
Channel signals open load.
702
AL SD DN BUTTON STR
Channel signals open load or internal error.
703
AL SD EXT SPEED DMD SW STR
Channel signals open load.
704
AL SD SPEED DMD INCREASE
STR
Channel signals open load or internal error.
DGC-2020HD
MTU Fault Codes