Horn configuration, Sender fail settings – Basler Electric DGC-2020HD User Manual
Page 199

9469300990 Rev B
189
Locator
Setting
Range
Increment
Unit
Low Oil Pressure Settings
L
Threshold
2.9 to 150
0.1
psi
0.2 to 10.3
0.1
bar
20 to 1034.5
0.1
kPa
High Coolant Temp Settings
M
Threshold
100 to 280
1
degrees F
38 to 138
1
degrees C
Low Coolant Temp Settings
N
Threshold
0 to 151
1
degrees F
–17 to 66
1
degrees C
Low Coolant Level Settings
O
Threshold
1 to 99
1
%
Maintenance Interval
P
Threshold
0 to 5,000
1
hours
Horn Configuration
BESTCOMSPlus
®
Navigation Path: Settings Explorer, Alarm Configuration, Horn Configuration
Front Panel Navigation Path: Settings > Alarm Configuration > Horn Configuration
To configure the audible horn using BESTCOMSPlus, open the Horn Configuration screen (Figure 130).
Figure 130. Settings Explorer, Alarm Configuration, Horn Configuration
An output contact is configured through programmable logic to energize an audible horn when an alarm
or pre-alarm condition exists. The horn settings consist of an enable/disable setting and a Not in Auto
enable/disable setting. If enabled, the contact output is closed when an alarm condition exists. The
contact output is toggled between open and closed when a pre-alarm condition exists. If the Not in Auto
setting is enabled, the horn is disabled when the DGC-2020HD is not operating in Auto mode.
Sender Fail Settings
BESTCOMSPlus
®
Navigation Path: Settings Explorer, Alarm Configuration, Sender Fail
Front Panel Navigation Path: Settings > Alarm Configuration > Sender Fail
To configure sender failure alarms using BESTCOMSPlus, open the Sender Fail screen (Figure 131).
Settings are listed in Table 52.
Coolant temperature, oil pressure, fuel level, and voltage sensing sender failure settings consist of an
alarm configuration setting and an activation delay. The alarm configuration setting allows selection of the
type of alarm to be annunciated when a sender fail condition exists. Status Only, Alarm, and Pre-alarm
can be selected. The selected alarm type is triggered when a sender failure exists for the duration of the
activation time delay.
DGC-2020HD
Reporting and Alarms