Ul approval, Csa certification, Nfpa compliance – Basler Electric DGC-2020HD User Manual
Page 24: Ce compliance, Physical

14
9469300990 Rev B
Salt Fog ............................................ IEC 60068
Ingress Protection ............................ IEC IP56 for front panel
Humidity ........................................... IEC 68-2-78
UL Approval
The DGC-2020HD is recognized to applicable Canadian and US safety standards and requirements by
UL.
Standards used for evaluation:
•
UL6200
•
CSA C22.2 No. 0
•
CSA C22.2 No. 14
The DGC-2020HD ground fault protection circuit complies with the Calibration and Withstand tests of UL
1053; as required by UL6200.
(See the Time Curve Characteristics chapter for the listing of curves verified to meet UL1053.)
Caution
To follow UL guidelines, replacement of the backup battery for the real-time clock
should be performed only by qualified personnel.
CSA Certification
The DGC-2020HD was tested and has met the certification requirements for electrical, plumbing and/or
mechanical products.
Standards used for evaluation:
•
CSA C22.2 No. 0
•
CSA C22.2 No. 14
NFPA Compliance
Complies with NFPA Standard 110, Standard for Emergency and Standby Power.
CE Compliance
This product has been evaluated and complies with the relevant essential requirements set forth by the
EU legislation.
EC Directives:
•
Low Voltage Devices (LVD) – 2006/95/EC
•
Electromagnetic Compatibility (EMC) – 2004/108/EC
Harmonized Standards used for evaluation:
•
EN 50178 - Electronic Equipment for use in Power Installations
•
EN 61000-6-4 - Electromagnetic Compatibility (EMC), Generic Standards, Emission Standard for
Industrial Environments
•
EN 61000-6-2 - Electromagnetic Compatibility (EMC), Generic Standards, Immunity for Industrial
Environments
Physical
Weight .............................................. 5.50 lb (2.5 kg)
Dimensions....................................... See the Mounting chapter.
Specifications
DGC-2020HD