Operating power, Aem-2020 inputs and outputs – Basler Electric DGC-2020HD User Manual
Page 317

9469300990 Rev B
307
DGC-2020HD
AEM-2020
Caution
By mating conductors of dissimilar metals, galvanic corrosion could
occur which may lead to signal loss.
Connector screw terminals accept a maximum wire size of 12 AWG (3.31 mm
2
). Thermocouple
connectors accept a maximum thermocouple wire diameter of 0.177 inches (4.5 mm). Maximum screw
torque is 5 inch-pounds (0.56 N
m).
Operating Power
The Analog Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. While reverse
polarity will not cause damage, the AEM-2020 will not operate. Operating power terminals are listed in
Table 84.
It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
Analog Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended.
Table 84. Operating Power Terminals
Terminal
Description
P1-
(SHIELD)
Chassis ground connection
P1-
– (BATT–)
Negative side of operating power input
P1- + (BATT+)
Positive side of operating power input
AEM-2020 Inputs and Outputs
Input and output terminals are shown in Figure 187 and listed in Table 85.