Figure 56 – Basler Electric DGC-2020HD User Manual
Page 119

9469300990 Rev B
109
Figure 56. Synchronizer Setup in BESTlogicPlus Step 13
14.
If using analog outputs to bias the voltage regulator and governor, no further setup is necessary. If
using output contacts, they must be set up to drive these functions. In BESTlogicPlus programmable
logic, click on the Elements tab. Drag the GOVR and AVR logic blocks into the main logic screen.
See Figure 57.
DGC-2020HD
Synchronizer