Generator voltage sensing, Bus voltage sensing, Engine sender inputs – Basler Electric DGC-2020HD User Manual

Page 30

background image

20

9469300990 Rev B

Caution

Current sensing terminals 2 (IA–), 4 (IB–), 6 (IC–), 8(AUX I1–), 10
(AUX I2–), 12 (AUX I3–), and 14 (AUX I4–) must be terminated to
ground for proper operation.

Note

Unused current sensing inputs should be shorted to minimize noise
pickup.

Generator Voltage Sensing

The DGC-2020HD accepts either line-to-line or line-to-neutral generator sensing voltage over the range of
0 to 576 volts, rms line-to-line or 0 to 333 volts, rms line-to-neutral. Generator voltage sensing terminals
are listed in Table 5.

Table 5. Generator Voltage Sensing Terminals

Terminal

Description

86 (GEN VA)

A-phase generator voltage sensing input

88 (GEN VB)

B-phase generator voltage sensing input

90 (GEN VC)

C-phase generator voltage sensing input

91 (GEN VN)

Neutral generator voltage sensing input

Bus Voltage Sensing

Sensing of bus voltage enables the DGC-2020HD to detect failures of the mains (utility). Controllers with
style number xxx2xxxxx use bus voltage sensing to perform automatic synchronization of the generator
with the bus. The DGC-2020HD accepts either line-to-line or line-to-neutral bus sensing voltage over the
range of 0 to 576 volts, rms line-to-line or 0 to 333 volts, rms line-to-neutral. Controllers with style number
xxxxxxxEx are equipped with two bus sensing inputs. One is intended for sensing the mains voltage while
the other is intended for sensing the load bus voltage.

Bus voltage sensing terminals are listed in Table 6.

Table 6. Bus Voltage Sensing Terminals

Terminal

Description

93 (BUS1 VA)

A-phase bus voltage sensing input

95 (BUS1 VB)

B-phase bus voltage sensing input

97 (BUS1 VC)

C-phase bus voltage sensing input

98 (BUS1 VN)

Neutral bus voltage sensing input

100 (BUS2 VA)

A-phase bus voltage sensing input (optional)

101 (BUS2 VB)

B-phase bus voltage sensing input (optional)

103 (BUS2 VC)

C-phase bus voltage sensing input (optional)

104 (BUS2 VN)

Neutral bus voltage sensing input (optional)

Engine Sender Inputs

Inputs are provided for fuel level, oil pressure, and coolant temperature senders. For a listing of fuel level,
oil pressure, and coolant temperature senders that are compatible with the DGC-2020HD, refer to the

Terminals and Connectors

DGC-2020HD