beautypg.com

Load sharing, Event recording, Data logging – Basler Electric DGC-2020HD User Manual

Page 12: Contact inputs and outputs, Automatic transfer switch control (mains failure), Device security

background image

2

9469300990 Rev B

Load Sharing

The DGC-2020HD provides analog outputs to the power system in the form of analog bias signals to the

voltage regulator and speed governor. A pulse width modulated (PWM) speed bias output is also

available. When the generator breaker is closed and load sharing is enabled, the DGC-2020HD shares

the real power load proportionally with other generators in the system. Load sharing can be implemented

on the Analog Load Share Line or through Ethernet communications. Reactive power (kvar) sharing is

accomplished through Ethernet communications.

Event Recording

A history of system events are logged in nonvolatile memory. The DGC-2020HD retains records for 128

unique types of events. Each record tracks the number of times that an event has occurred and records a

time stamp of the first and last occurrences.
A Sequence of Events (SER) log is also available. This log tracks the internal and external status of the

DGC-2020HD. Events are scanned at five millisecond intervals with 1,023 events stored per record. All

changes of state that occur during each scan are time- and date-stamped. Sequences of Events reports

are available through BESTCOMSPlus. Over 1,000 records can be retained in nonvolatile memory. When

the SER memory becomes full, the oldest record is replaced by the latest one acquired.

Data Logging

The data logging function of the DGC-2020HD records up to six records of user-selectable, real-time

parameter data. For more information, see the Reporting and Alarms chapter.

Contact Inputs and Outputs

DGC-2020HD controllers have 16 programmable contact inputs. All contact inputs recognize dry contacts.

The programmable inputs can be configured to initiate a pre-alarm or alarm condition. A programmable

input can be programmed to receive a contact input from an automatic transfer switch (ATS). In addition,

a programmable Battle Override function allows overriding of DGC-2020HD alarms and protection

functions. Each programmable input can be assigned a user-defined name for easy identification at the

front panel display and in fault records.
Output contacts include three dedicated relays for energizing an engine’s glow plugs, fuel solenoid, and

starter solenoid. An additional twelve programmable output contacts are provided.
Additional contact inputs and output contacts can be accommodated with an optional CEM-2020 Contact

Expansion Module. Contact Basler Electric for ordering information.

Automatic Transfer Switch Control (Mains Failure)

The DGC-2020HD has the ability to detect a mains failure via a single- or three-phase Bus input. A mains

failure is established when any one of the following conditions are met:

Any phase of bus voltage falls below the dead bus threshold

Any phase of bus voltage is unstable due to overvoltage or undervoltage

Any phase of bus voltage is unstable due to overfrequency or underfrequency

At this time, the DGC-2020HD starts the genset and, when ready, applies power to the load from the

genset. The DGC-2020HD implements open or closed breaker transitions to and from the mains. When

the mains returns and is considered stable, the DGC-2020HD will transfer the load back to the mains and

stop the engine. During closed breaker transitions, the optional Auto Synchronizer can synchronize the

generator to the mains before transferring the load from generator power to utility power.

Device Security

Passwords provide access security for six distinct functional access areas: Read, Control, Operator,

Settings, Design, and Administrator. Each username/password is assigned an access area with access to

that area and each area below it. An administrator password provides access to all six of the functional

areas.

Introduction

DGC-2020HD