Basler Electric DGC-2020HD User Manual
Page 379
9469300990 Rev B
369
Fault
Code
String
Description
118
LO ECU SUPPLY VOLTS
Power supply voltage too low (limit 1).
119
LOLO ECU SUPPLY VOLTS
Power supply voltage too low (limit 2).
120
HI ECU SUPPLY VOLTS
Power supply voltage too high (limit 1).
121
HIHI ECU SUPPLY VOLTS
Power supply voltage too high (limit 2).
122
HI T ECU
Temperature of electronic too high (limit 1).
134
15v POSECU DEFCT
Internal electronic fault.
136
15V NEGECU DEFCT
Internal electronic fault.
137
L1 5V BUFFR TEST
Pressure-sensor fault, pressure-sensor wiring, or internal electronic
fault.
138
SENSOR PWR DEFCT
Pressure-sensor fault, pressure-sensor wiring, or internal electronic
fault.
139
L1 TE BUFFR TEST
Internal electronic fault.
140
TE BUF ECU DEFCT
Internal electronic fault.
141
AL POWER TOO HIGH
AL power too high.
142
MCR EXCEEDED 1 HR STR
AL MCR exceeded 1 hour.
143
BANK1 ECU DEFECT
Internal electronic fault.
144
BANK2 ECU DEFECT
Internal electronic fault.
145
15V GOODECU DFCT
Internal electronic fault.
147
AD TST1ECU DEFCT
Internal electronic fault.
149
AD TST2ECU DEFCT
Internal electronic fault.
151
AD TST3ECU DEFCT
Internal electronic fault.
170
MI MODULE FAIL
Module in maintenance indicator defect.
171
MI NOT ACTIVE
WI not active anymore.
172
TBO EXPIRED
TBO expired.
173
MODL WRITE LIMIT
EEPROM write limit reached.
176
AL LIFE DATA NA
No (fitting) LifeData-Backup-System is available within a delay time
after ECU Reset.
177
AL LIFE DATA INCPLT
If the ADEC has to restore the LifeData from the backup-system
and at least one checksum is wrong after the upload or the upload
is incomplete, then this failure is set.
180
AL CAN1 NODE LOST
Connection to a node on CAN 1 lost.
181
AL CAN2 NODE LOST
Connection to a node on CAN 2 lost.
182
AL CAN WRONG PARAMS
Incorrect CAN parameter values have been entered.
183
AL CAN NO PU DATA
A CAN mode is selected which the communication is initialized
aided of the PU data module. However, required PU data module is
not present or is not valid.
184
AL CAN PUDATA ERR
During attempt to copy a received PU data module to Flash
module, a program error occurred.
185
CAN LESS MAILBXS
CAN less mailboxes.
186
AL CAN1 BUS OFF
CAN controller 1 is in “Bus Off” state.
187
AL CAN1 ERR PASSV
CAN controller 1 has signaled a warning.
188
AL CAN2 BUS OFF
CAN controller 2 is in “Bus Off” state.
189
AL CAN2 ERROR PASSV
CAN controller 2 has signaled a warning.
190
AL EMU PARAM NO SUPPORT
EMU parameters are not supported.
201
SD T COOLANT
Coolant temperature-sensor defect.
DGC-2020HD
MTU Fault Codes