Time Dial Increment ......................... 0.1
Inverse Time Curves ........................ See the Time Overcurrent Characteristic Curves chapter
Caution
For 1 A current sensing, current shall not exceed 3 amperes for 30
seconds or 4 amperes for 1 second. For 5 A current sensing, current
shall not exceed 15 amperes for 30 seconds or 20 amperes for 1
second. Exceeding the above limits may result in equipment damage.
Phase Voltage Imbalance (47) (Optional)
Pickup Range ................................... 0 to 150 Vac
Pickup Increment ............................. 1 Vac
Hysteresis Range ............................. 1 to 5 Vac
Activation Delay Range .................... 0 to 600 s
Activation Delay Increment .............. 0.1 s
Vector Shift (78) (Optional)
Pickup Range ................................... 2 to 90°
Pickup Increment ............................. 1°
Hysteresis......................................... 0.5 degrees
Accuracy...........................................
±1°
Logic Timers
Hours Setting Range ........................ 0 to 250
Hours Setting Increment .................. 1
Minutes Setting Range ..................... 0 to 59
Minutes Setting Increment ............... 1
Seconds Setting Range ................... 0 to 59
Seconds Setting Increment .............. 1
Accuracy...........................................
±15 ms
Communication Interface
CAN (SAE J1939)
Differential Bus Voltage .................... 1.5 to 3 Vdc
Maximum Voltage ............................ –32 to +32 Vdc with respect to negative battery terminal
Communication Rate ........................ 250 kb/s
CAN 1 Terminals .............................. 51 (low), 52 (high), and 53 (shield)
CAN 2 Terminals .............................. 54 (low), 55 (high), and 53 (shield)
Notes
1.
If the DGC-2020HD is providing one end of the J1939 bus, a 120
Ω, ½ watt
terminating resistor should be installed across terminals 51 (CAN1L) and 52
(CAN1H) and/or 54 (CAN2L) and 55 (CAN2H).
2.
If the DGC-2020HD is not part of the J1939 bus, the stub connecting the DGC-
2020HD to the bus should not exceed 914 mm (3 ft) in length.
3.
The maximum bus length, not including stubs, is 40 m (131 ft).
4.
The J1939 drain (shield) should be grounded at one point only. If grounded
elsewhere, do not connect the drain to the DGC-2020HD.
DGC-2020HD
Specifications