beautypg.com

Operating power, Generator current sensing, Programmable current sensing – Basler Electric DGC-2020HD User Manual

Page 29

background image

9469300990 Rev B

19

Operating Power

The DGC-2020HD operating power input accepts a nominal voltage of 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. While reverse
polarity will not cause damage, the DGC-2020HD will not operate. Operating power terminals are listed in
Table 2.

A fuse should be added for additional protection for the wiring to the battery input of the DGC-2020HD. A
fuse helps prevent wire damage and nuisance trips due to initial power supply inrush current. To follow
UL guidelines, a 5 A maximum, 32 Vdc supplementary fuse must be implemented in the battery input
circuit to the DGC-2020HD.

Table 2. Operating Power Terminals

Terminal

Description

50 (CHASSIS)

Chassis ground connections

49 (BATT–)

Negative side of operating power input

48 (BATT+)

Positive side of operating power input

Generator Current Sensing

The DGC-2020HD has sensing inputs for A-phase, B-phase, and C-phase generator current. A DGC-
2020HD with a style number of 1xxxxxxxxx has 1 Aac nominal current sensing and a DGC-2020HD with a
style number of 5xxxxxxxx indicates 5 Aac nominal current sensing. Generator current sensing terminals
are listed in Table 3.

Table 3. Generator Current Sensing Terminals

Terminals

Description

1 (IA+)

A-phase current sensing input

2 (IA–)

3 (IB+)

B-phase current sensing input

4 (IB–)

5 (IC+)

C-phase current sensing input

6 (IC–)

Programmable Current Sensing

Four user-programmable current sensing inputs are provided for measuring mains current, load bus
current, ground current, or a combination of these. Table 4 lists the programmable current sensing
terminals.

Table 4. Programmable Current Sensing Terminals

Terminal

Description

7 (AUX I1 +)

Programmable current sensing input 1

8 (AUX I1 –)

9 (AUX I2 +)

Programmable current sensing input 2

10 (AUX I2 –)

11 (AUX I3 +)

Programmable current sensing input 3

12 (AUX I3 –)

13 (AUX I4 +)

Programmable current sensing input 4

14 (AUX I4 –)

DGC-2020HD