Remote analog outputs configuration – Basler Electric DGC-2020HD User Manual
Page 329

9469300990 Rev B
319
DGC-2020HD
AEM-2020
Figure 200. Settings Explorer, Programmable Inputs, Remote Analog Inputs, AEM 1 Thermocouple Input #1
Table 89. Settings for AEM x Thermocouple Input #y
Locator
Setting
Range
Increment
Unit
A
Label Text
n/a
n/a
n/a
B
Arming Delay
0 to 300
1
seconds
C
Hysteresis
0 to 100
0.1
%
D
Mode
Disabled, Over, or
Under
n/a
n/a
E
Threshold
0 to 1,375
1
degrees C
32 to 2,507
1
degrees F
F
Activation Delay
0 to 300
1
seconds
G
Alarm Configuration
Status Only, Pre-
Alarm, or Alarm
n/a
n/a
Remote Analog Outputs Configuration
Four remote analog outputs provide voltage or current signals from the AEM-2020 to a variety of industrial
transducers.
The four, identical remote analog outputs are designated AEM x Output #1 through AEM x Output #4
(where x = 1 to 4). Remote analog output operational settings are configured on the AEM x Output #y
(where x = 1 to 4 and y = 1 to 4) settings screen in BESTCOMSPlus.
BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Outputs, Remote Analog Outputs
Front Panel Navigation Path: Settings Explorer > Programmable Outputs > Remote Analog Outputs