Remote analog outputs configuration – Basler Electric DGC-2020HD User Manual

Page 329

background image

9469300990 Rev B

319

DGC-2020HD

AEM-2020

Figure 200. Settings Explorer, Programmable Inputs, Remote Analog Inputs, AEM 1 Thermocouple Input #1

Table 89. Settings for AEM x Thermocouple Input #y

Locator

Setting

Range

Increment

Unit

A

Label Text

n/a

n/a

n/a

B

Arming Delay

0 to 300

1

seconds

C

Hysteresis

0 to 100

0.1

%

D

Mode

Disabled, Over, or

Under

n/a

n/a

E

Threshold

0 to 1,375

1

degrees C

32 to 2,507

1

degrees F

F

Activation Delay

0 to 300

1

seconds

G

Alarm Configuration

Status Only, Pre-

Alarm, or Alarm

n/a

n/a

Remote Analog Outputs Configuration

Four remote analog outputs provide voltage or current signals from the AEM-2020 to a variety of industrial
transducers.

The four, identical remote analog outputs are designated AEM x Output #1 through AEM x Output #4
(where x = 1 to 4). Remote analog output operational settings are configured on the AEM x Output #y
(where x = 1 to 4 and y = 1 to 4) settings screen in BESTCOMSPlus.

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Outputs, Remote Analog Outputs
Front Panel Navigation Path:
Settings Explorer > Programmable Outputs > Remote Analog Outputs