Name

Description

Symbol

CEM
Unsupported
Number

True when more CEM-2020s are connected
than are configured on the System
Parameters, Remote Module Setup screen
in BESTCOMSPlus.

CEM x Comm
Fail

True when communication from the CEM-
2020 to the DGC-2020HD has been lost.

CEM x
Hardware
Mismatch

True when the connected CEM-2020 does
not have the same number of outputs as
defined on the System Parameters, Remote
Module Setup screen in BESTCOMSPlus.

CEM x Not
Configured

True when the expected serial number on
the System Parameters, Remote Module
Setup screen in BESTCOMSPlus does not
match the serial number detected on the
General Settings, Device Info screen.

Configurable Protection

Configurable
Protection
Threshold x

True when the Alarm Configuration is set to
Pre-Alarm and the threshold has been
exceeded.

Generator Protection

Frequency

True when the 81-x element is configured as
a pre-alarm and has tripped.

Loss of
Excitation

True when the 40Q-x element is configured
as a pre-alarm and has tripped.

Overcurrent

True when the 51-x element is configured as
a pre-alarm and has tripped.

Overvoltage

True when the 59-x element is configured as
a pre-alarm and has tripped.

Phase
Imbalance

True when the 47-x element is configured as
a pre-alarm and has tripped.

Power

True when the 32-x element is configured as
a pre-alarm and has tripped.

Undervoltage

True when the 27-x element is configured as
a pre-alarm and has tripped.

Vector Shift

True when the 78-x element is configured as
a pre-alarm and has tripped.

Programmable Inputs

Analog Inputs
Out of Range

True when the analog input connection is
open and the Out of Range Alarm Type is
set to Pre-Alarm.

Analog Inputs
Threshold

True when the Alarm Configuration is set to
Pre-Alarm and the threshold has been
exceeded.

Contacts Inputs
Input x

True when Contact Input x is active, the
Alarm Configuration is set to Pre-Alarm, and
the activation delay has expired.

Remote Analog
Inputs
Out of Range

True when the remote analog input
connection is open and the Out of Range
Alarm Type is set to Pre-Alarm.