Basler Electric DGC-2020HD User Manual
Page 353

9469300990 Rev B
343
Relay Equation
When the 46 function is used, the relay uses the K factor (i.e., 46 time dial setting), 46 minimum pickup
setting, and generator full-load current to create a constant Z (see Equation 13).
𝑍 = 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �
𝐼
𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔
46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔�
2
Equation 13
The time to trip equation used in the relay is:
𝑇
𝑇
=
𝑍
𝑀
2
+ 0.028 𝑠𝑒𝑐𝑜𝑛𝑑𝑠
Equation 14
where:
𝑀 =
𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑 𝐼
2
46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔
Equation 15
which, when M > 1, reduces to:
𝑇
𝑇
= 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �
𝐼
𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔
𝐼
2
𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑�
2
Equation 16
DGC-2020HD
Time Curve Characteristics
See also other documents in the category Basler Electric Accessories for electrical:
- SMC-250 (6 pages)
- AVC63-2 (2 pages)
- AVC63-2.5 (2 pages)
- AVC63-4D (6 pages)
- AVC63-7 (4 pages)
- AVC63-7F (4 pages)
- AVC Sensing Module (2 pages)
- AVC125-10 (10 pages)
- AVC125-10 (14 pages)
- APR63-5 (6 pages)
- APR63-5X (4 pages)
- DECS-400 (250 pages)
- BE350 (4 pages)
- VR63-4/UL (2 pages)
- VR63-4A/UL (4 pages)
- VR63-4B (2 pages)
- VR63-4C/UL (2 pages)
- BE300PM (4 pages)
- DECS-100 (86 pages)
- DECS-250N Terminals and Connectors (370 pages)
- DECS-250 Mounting (4 pages)
- DECS-250N Mounting (4 pages)
- MVC232 (4 pages)
- MVC112 (8 pages)
- MVC236 (24 pages)
- BE2000E (82 pages)
- MVC300 (16 pages)
- CBS 212A (28 pages)
- MVC301 (16 pages)
- ICRM-15 (4 pages)
- DGC-2020 Troubleshooting (620 pages)
- DGC-2020ES (252 pages)
- DGC-2020ES Mounting (2 pages)
- DGC-2020HD Modbus Protocol (318 pages)
- RDP-110 (26 pages)
- BE1-25A (90 pages)
- IDP-800 (70 pages)
- ESD201 (4 pages)
- ESD202 (2 pages)
- IDP-1200 (90 pages)