Introduction, Features and functions, Generator and bus protection and metering – Basler Electric DGC-2020HD User Manual
Page 11: Engine protection and metering

9469300990 Rev B
1
Introduction
The DGC-2020HD Digital Genset Controller provides integrated engine-genset control, protection, and
metering in a single package. Microprocessor based technology allows for exact measurement, setpoint
adjustment, and timing functions. Front panel controls and indicators enable quick and simple DGC-
2020HD operation. A backlit liquid crystal display (LCD) can be viewed under a wide range of ambient
light and temperature conditions. Basler Electric communication software (BESTCOMSPlus®) allows units
to be easily customized for each application. Because of the low sensing burden in the DGC-2020HD,
dedicated potential transformers (PTs) are not required.
Features and Functions
The DGC-2020HD Digital Genset Controller has the following features:
•
Local and remote generator control
•
Engine, generator, and loss of mains protection (optional)
•
Automatic transfer switch control (mains failure)
•
Automatic generator configuration detection
•
Generator sequencing
•
Generator soft loading/unloading
•
Auto synchronizing (optional)
•
Programmable analog engine senders
•
16 programmable contact inputs
•
Three programmable front panel LEDs, with labels
•
Up to four local analog inputs
•
A ramping function to load and unload generator smoothly
•
Demand start/stop and generator sequencing
•
kW and kvar load control
•
kW and kvar load sharing via Ethernet or analog load share lines
•
Programmable logic
•
Exercise timer
•
ECU communications via SAE J1939
•
Marathon DVR2000E+ voltage regulator control via SAE J1939
•
Integrated USB, RS485, and Ethernet communication
•
Two J1939 CAN Bus ports
•
Additional modules available to expand the capabilities of the DGC-2020HD
An overview of DGC-2020HD Digital Genset Controller functions is provided in the following paragraphs.
Generator and Bus Protection and Metering
Multifunction protection guards against overvoltage, undervoltage, excessive forward and reverse power,
underfrequency, and overfrequency. Overcurrent, phase imbalance, loss of mains, and frequency rate-of-
change protection are available as an option. Each protection function has an adjustable pickup and time
delay setting. Sixteen inverse time curves, in addition to user-programmable curves, enable the DGC-
2020HD to offer overcurrent protection in a variety of applications. Each protective element can be
assigned to the generator, bus 1 or bus 2.
Metered generator and bus parameters include voltage, current, real power (watts), apparent power (VA),
and power factor (PF).
Engine Protection and Metering
Engine protection features include oil pressure and coolant temperature monitoring, overcrank protection,
ECU-specific protection elements, and diagnostic reporting.
Metered engine parameters include oil pressure, coolant temperature, battery voltage, speed, fuel level,
engine load, coolant level (from ECU), ECU-specific parameters, and run-time statistics.
DGC-2020HD
Introduction