Basler Electric DGC-2020HD User Manual
Page 127

9469300990 Rev B
117
Locator
Setting
Range
Increment
Unit
C
Correction Pulse Width
0 to 99.9
0.1
seconds
D
Correction Pulse Interval
0 to 99.9
0.1
seconds
Speed Settings
E
Kp Proportional Gain
0 to 1,000
0.001
n/a
F
Ki Integral Gain
0 to 1,000
0.001
n/a
G
Kd Derivative Gain
0 to 1,000
0.001
n/a
H
Td Derivative Gain
0 to 1
0.001
n/a
I
Kg Loop Gain
0 to 1,000
0.001
n/a
J
Speed Trim Enable
Disable or Enable
n/a
n/a
K
Speed Trim Setpoint
47 to 100
0.01
Hz
L
Remote Speed Bias Source
Aux Inputs 1 to 4 or
None
n/a
n/a
M
Remote Speed Bias
0 to 5
0.01
%
kW Settings
N
Load Control Enabled
Disable or Enable
n/a
n/a
O
Load Share Interface
Analog or Ethernet
n/a
n/a
P
Kp Proportional Gain
0 to 1,000
0.001
n/a
Q
Ki Integral Gain
0 to 1,000
0.001
n/a
R
Kd Derivative Gain
0 to 1,000
0.001
n/a
S
Td Derivative Filter Constant
0 to 1
0.001
n/a
T
Kg Loop Gain
0 to 1,000
0.001
n/a
U
Droop Percentage
0 to 10
0.001
%
V
Speed Droop Gain
0 to 1,000
0.001
n/a
W
Ramp Rate
0 to 100
0.1
% per second
X
Base Load Level
0 to 100
0.1
%
Y
Base Load Level Source
User Setting or Aux
Input 1 to 4
n/a
n/a
Z
Base Load Analog Max
0 to 100
0.1
%
AA
Base Load Analog Min
0 to 100
0.1
%
BB
Breaker Open Setpoint
0 to 100
0.1
%
DGC-2020HD
Bias Control