Basler Electric DGC-2020HD User Manual
Page 230
![background image](https://www.manualsdir.com/files/773949/content/doc230.png)
220
9469300990 Rev B
Name
Description
Symbol
Remote Analog
Inputs
Threshold
True when the Alarm Configuration is set to
Pre-Alarm and the threshold has been
exceeded.
Remote
Contact Inputs
Input x
True when Remote Contact Input x is active,
the Alarm Configuration is set to Pre-Alarm,
and the activation delay has expired.
Remote RTD
Inputs
Out of Range
True when the remote RTD input connection
is open and the Out of Range Alarm Type is
set to Pre-Alarm.
Remote RTD
Inputs
Threshold
True when the Alarm Configuration is set to
Pre-Alarm and the threshold has been
exceeded.
Remote
Thermocouple
Inputs
Threshold
True when the Alarm Configuration is set to
Pre-Alarm and the threshold has been
exceeded.
Programmable Outputs
Configurable
Elements
Element x
True when the Configurable Element x logic
element is true, Alarm Configuration is set to
Pre-Alarm, and the Activation Delay has
expired.
Remote Analog
Outputs
Out of Range
True when the remote analog output
connection is open and the Out of Range
Alarm Type is set to Pre-Alarm.
Senders
Coolant Temp
Sender Fail
True when the Coolant Temp Sender Fail is
configured as a pre-alarm and the activation
delay has expired.
Fuel Level
Sender Fail
True when the Fuel Level Sender Fail is
configured as a pre-alarm and the activation
delay has expired.
Oil Pressure
Sender Fail
True when the Oil Pressure Sender Fail is
configured as a pre-alarm and the activation
delay has expired.
Voltage
Sensing Fail
True when the Voltage Sensing Fail is
configured as a pre-alarm and the activation
delay has expired.
Table 61. I/O Group, Senders
Name
Description
Symbol
Coolant Temp
Sender Fail
True when the Coolant Temp Sender Fail is configured as
either a pre-alarm or alarm and the activation delay has expired.
Fuel Level
Sender Fail
True when the Fuel Level Sender Fail is configured as either a
pre-alarm or alarm and the activation delay has expired.
Oil Pressure
Sender Fail
True when the Oil Pressure Sender Fail is configured as either
a pre-alarm or alarm and the activation delay has expired.
Speed Sender
Fail
True when the Speed Sender Fail activation delay has expired.
BESTlogic
™Plus
DGC-2020HD