9469300990 Rev B
Fault
Code
String
Description
417
SD L WATER FUEL PREFILT
Water level-sensor of fuel pre-filter defect.
420
AL L1 AUX 1
Input of Aux 1 injured limit 1.
421
AL L2 AUX 1
Input of Aux 1 injured limit 2.
428
AL L1 T AUX 1
Temperature input of Aux 1 injured limit 1.
438
LO P FUEL RAIL 2 STR
Low pressure on fuel rail 2.
439
HI P FUEL RAIL 2 STR
Hi pressure on fuel rail 2.
440
AL L1 P AUX 1
Pressure input of Aux 1 injured limit 1.
441
AL RAIL 2 LEAKAGE STR
Alarm fuel rail 2 leak detected.
442
AL L2 P AUX 1
Pressure input of Aux 1 injured limit 2.
444
SD U PDU
Sensor defect of Injector Power driver unit.
445
SD P AMBIENT AIR
Ambient air pressure-sensor defect.
448
HI P CHARGE AIR
Pressure of charge air too high (limit 1).
449
SS P CHARGE AIR
Pressure of charge air too high (limit 2).
450
SD IDLE END TRQ IN
Input of Idle/End-Torque defect
454
SS PWR RED ACT
Power Reduction is activated.
455
AL L1 AUX1 PLANT
Input of Aux 1 (plant) injured limit 1.
456
AL L2 AUX1 PLANT
Input of Aux 1 (plant) injured limit 2.
461
LO T EXHAUST EMU
Exhaust gas temperature of EMU too low (limit 1).
462
HI T COOLANT EMU
Coolant temperature of EMU injured limit 1.
463
SD AUX 2
Sensor defect on Aux 2.
464
SD P AUX 1
Analog input for pressure Aux 1 defect.
467
AL L2 T AUX 1
Temperature input of Aux 1 injured limit 2.
468
SD T AUX 1
Analog input for Temperature Aux 1 defect.
469
SD AUX 1
Analog input for Aux 1 defect.
470
SD T ECU
ECU temperature-sensor defect.
471
SD COIL CURRENT
Coil Current sensor defect.
472
AL STOP SD
Engine stop, because critical channel has sensor defect.
473
AL WIRING PWM CM2
Open load or short circuit on channel PWM_CM2.
474
AL WIRING FREQ OUT
Open load or short circuit on frequency output (FO) channel.
475
AL CR TRIG ENG ST
Released in case of an engine stop in order to trigger the crash
recorder.
476
AL CRASH REC ERR
Initial error of crash recorder.
478
AL COMB ALM YEL
Combined Alarm YELLOW (Plant).
479
AL COMB ALM RED
Combined Alarm RED (Plant).
480
AL EXT ENG PROT
External Engine Protection function active.
500
AL WIRING POM STARTER 1
A wiring fault has been detected in the connection of starter 1 of
POM.
501
AL WIRING POM STARTER 2
A wiring fault has been detected in the connection of starter 2 of
POM.
502
AL OPEN LD POM ALTRNATR
An open load on POM’s alternator output has been detected.
503
AL BATT NOT CHARGING
Battery is not being charged by alternator.
504
AL CAN POM NODE LOST
POM is missing on CAN bus.
505
AL NEW POM FOUND
New POM found.