Pre-start, Restart – Basler Electric DGC-2020HD User Manual
Page 278

268
9469300990 Rev B
Figure 171. Settings Explorer, System Parameters, Crank Settings
Table 78. Settings for Crank Settings
Locator
Setting
Range
Increment
Unit
A
Pre-crank Delay
0 to 30
1
seconds
B
Restart Delay
0 to 120
1
seconds
C
Number of Crank Cycles
1 to 7
1
n/a
D
Cycle Crank Time
5 to 15
1
seconds
E
Continuous Crank Time
5 to 60
1
seconds
F
Crank Disconnect Limit
10 to 100
1
%
G
Crank Disconnect Pressure
2.9 to 150
0.1
psi
0.2 to 10.3
0.1
bar
20 to 1,034.5
0.1
kPa
H
Off Mode Cool Down Enable
Disable or Enable
n/a
n/a
I
No Load Cool Down Time
0 to 60
1
minutes
Pre-Start
If desired, cranking can be delayed after initiating engine startup. During this delay, the Pre-Start output
closes to energize glow plugs or pre-start lubrication pumps. The Pre-crank Delay setting accepts values
from 0 to 30, in increments of 1 second.
The Pre-Start output can be configured to open upon conclusion of engine cranking or remain closed
while the engine is running.
The Pre-Start output can be configured during the resting state. If Preheat Before Crank is selected, the
Pre-Start output is closed for the duration of the Pre-crank Delay time prior to re-entering the cranking
state. If the Pre-crank delay setting is longer than the rest interval, the Pre-Start output is closed for the
entire duration of the rest time.
Restart
Attempting to start an engine after a normal shutdown but before the engine RPM has settled to zero can
stress an engine in certain situations. The Restart Delay inhibits attempts to start the engine immediately
after a normal shutdown for the duration of the Restart Delay timer. This delay should allow an engine to
Configuration