Basler Electric DGC-2020HD User Manual
Page 225

9469300990 Rev B
215
Name
Description
Symbol
Senders
Coolant Level
Sender Fail
True when a low coolant level error status code is
received from the ECU. CAN bus must be
enabled.
Coolant Temp
Sender Fail
True when the Coolant Temp Sender Fail is
configured as an alarm and the activation delay
has expired.
Fuel Level
Sender Fail
True when the Fuel Level Sender Fail is
configured as an alarm and the activation delay
has expired.
Oil Pressure
Sender Fail
True when the Oil Pressure Sender Fail is
configured as an alarm and the activation delay
has expired.
Speed Sender
Fail
True when the Speed Sender Fail activation
delay has expired.
Voltage
Sensing Fail
True when the Voltage Sensing Fail is configured
as an alarm and the activation delay has expired.
User Programmable Alarms
Programmable
Alarm x
True when the User Programmable Alarm x logic
element is true and the Activation Delay has
expired.
Table 60. I/O Group, Pre-Alarms
Name
Description
Symbol
AVR Output
Out of Range
True when AVR Output is the selected
parameter, Out of Range Alarm Type is set
to Pre-Alarm, and the threshold has been
exceeded.
Battery Charger
Fail
True when the Fuel Leak Detect function is
configured as an alarm and the activation
delay has expired.
Bus x Reverse
Rotation Status
True when the Bus x rotation is opposite of
the Phase Rotation setting.
DEF Engine
Derate
This pre-alarm indicates the lowest level of
inducement not to operate the engine when
Diesel Exhaust Fluid (DEF) is low or of poor
quality or there is a problem with the
Exhaust After Treatment System (EATS).
The engine is operating in a reduced power
mode. Eventually the level of inducement will
be increased unless the problem with the
DEF or malfunction in the EATS is corrected.
DEF Fluid
Empty
True when the engine ECU reports via CAN
bus that Diesel Exhaust Fluid (DEF) is at a
level below 8%.
DEF Fluid Low
True when the engine ECU reports via CAN
bus that the Diesel Exhaust Fluid (DEF) is at
a level between 8 and 23%.
DEF
Inducement
Override
This pre-alarm indicates a temporary
override of inducement not to operate the
engine. This is set by the ECU and is not a
user setting.
DGC-2020HD
BESTlogic
™Plus