Basler Electric DGC-2020HD User Manual
Page 218
![background image](https://www.manualsdir.com/files/773949/content/doc218.png)
208
9469300990 Rev B
Name
Description
Symbol
Fuel Leak
Detect
True when the Fuel Leak Detect input is
true, the Alarm Type is set to Status Only,
and the activation delay has expired.
Generator
Breaker Status
True when the generator breaker is closed.
Generator Dead
True when the Gen Dead condition settings
have been exceeded.
Generator Fail
True when the Gen Fail condition settings
have been exceeded.
Generator
Forward
Rotation
True when the generator rotation matches
the Phase Rotation setting.
Generator
Reverse
Rotation Status
True when the generator rotation is
opposite of the Phase Rotation setting.
Generator
Stable
True when the Gen Stable condition
settings have been exceeded.
Generator Test
True when the Exercise Timer has started
the generator.
Generator Test
Loaded
True when the Exercise Timer has started
the generator and Run with Load is
selected.
GOV Output
Out of Range
True when the GOV Output Limit settings
have been exceeded.
Grounded Delta
Override
True when the Grounded Delta Override
input is true.
Idle Request
True when the Idle Request logic element
is true.
Lamp Test
True when the Lamp Test logic element is
true or the Lamp Test button is pressed on
the front panel.
Load Take Over
True when the Load Take Over logic
element is true.
Low Coolant
Level
True when the Low Coolant Level function
is configured as an alarm or pre-alarm and
the activation delay has expired. In
addition, true when CAN bus is enabled
and the Low Coolant Level Alarm or Pre-
Alarm threshold has been exceeded.
Low Line
Override
True when the Low Line Override logic
element is true.
LS Output Out
of Range
True when the LS Output Limit settings
have been exceeded.
Mains Breaker
Status
True when the mains breaker is closed.
BESTlogic
™Plus
DGC-2020HD