Basler Electric DGC-2020HD User Manual
Page 258

248
9469300990 Rev B
CAN Bus 2 Address
This parameter sets a unique address number for the DGC-2020HD operating on CAN 2 (ECU). The
CAN Address is set internally by the DGC-2020HD when certain types of ECUs are selected on the ECU
Setup screen, and in this case, the user-entered value does not apply.
ECU Related Time Values - Response Timeout
This setting defines the amount of time that the DGC-2020HD will wait to receive data from the ECU
during a pulse cycle or start attempt. If no data is received during this time in a pulse cycle, a LOSS OF
ECU COMMS pre-alarm is annunciated. If no data is received in this time during an engine starting
attempt, a LOSS OF ECU COMMS alarm is annunciated.
Generator Parameter Transmit
When the Generator Parameter Transmit setting is enabled, the DGC-2020HD broadcasts generator
metered parameters over CAN as listed in Table 70. The Generator Parameter Transmit setting is not
used when ECU Type is set for MTU MDEC, MTU ECU7/ECU8, or MTU Smart Connect.
Table 70. Transmitted Generator Parameters
PGN Name
PGN
(Hex)
SPN
Parameter
Units
Scaling /
Offset
Bytes
Within
PGN
Data
Generator
Total AC
Energy
65018
(FDFA)
2468
Generator Total kW Hours
Export
kWH
n/a
1 to 4
2469
Generator Total kW Hours
Import
kWH
n/a
5 to 8
Generator
Total AC
Reactive
Power
65028
(FE04)
2456
Generator Total Reactive Power
vars
n/a
1 to 4
2464
Generator Overall Power Factor
PF
∗
16,384
-1 offset
5 to 6
2518
Generator Overall Power Factor
Lagging
n/a
00=leading
01=lagging
10=error
11=not
available
7, bits
1 & 2
Generator
Total AC
Power
65029
(FE05)
2452
Generator Total Real Power
Watts
n/a
1 to 4
2460
Generator Total Apparent Power
VA
n/a
5 to 8
Generator
Average
Basic AC
Quantities
65030
(FE06)
2440
Generator Average L-L AC RMS
Voltage
Volts
n/a
1 to 2
2444
Generator Average L-N AC RMS
Voltage
Volts
n/a
3 to 4
2436
Generator Average AC
Frequency
Hz
∗
128
n/a
5 to 6
2448
Generator Average AC RMS
Current
Amps
n/a
7 to 8
Communication
DGC-2020HD