Bulletin 280/281 Programmable Parameters
3-15
OutA Pr FltValue
This parameter determines the
state the Out A assumes when a
trip occurs and Parameter 33 is
set to “0”
0 = Open
1 = Close
Parameter Number
34
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN FltState
This parameter in conjunction
with Parameter 36 defines how
Output A will respond when a
DeviceNet network fault occurs.
When set to “1”, Output A will
hold state prior to trip
occurrence. When set to “0”,
Output A will open or close as
determined by setting in
Parameter 36
Parameter Number
35
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN FltValue
This parameter determines the
state that Output A assumes
when a DeviceNet network fault
occurs and Parameter 35 is set to
“0”
0 = Open
1 = Close
Parameter Number
36
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN IdlState
This parameter in conjunction
with Parameter 38 defines how
Output A will respond when the
DeviceNet network is idle. When
set to “0”, Output A will open or
close as determined by the
setting in Parameter 38 The
DN Flt parameters supersede the
Dn Idl parameters
Parameter Number
37
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN IdlValue
This parameter determines the
state that Output A assumes
when the network is idle and
Parameter 37 is set to “0”
0 = Open
1 = Close
Parameter Number
38
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0