Bulletin 283 Programmable Parameters
4-19
OutB Pr FltValue
This parameter determines the
state the Out B assumes when a
protection trip occurs and
Parameter 39 is set to “0”
0 = Open
1 = Close
Parameter Number
40
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB DN FltState
This parameter in conjunction
with Parameter 42 defines how
Output B will respond when a
DeviceNet network fault occurs.
When set to “1”, Output B will
hold state prior to trip
occurrence. When set to “0”,
Output B will open or close as
determined by setting in
Parameter 42
Parameter Number
41
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB DN FltValue
This parameter determines the
state that Output B assumes
when a DeviceNet network fault
occurs and Parameter 41 is set to
“0”
0 = Open
1 = Close
Parameter Number
42
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB DN IdlState
This parameter in conjunction
with Parameter 44 defines how
Output B will respond when the
DeviceNet network is idle. When
set to “0”, Output B will open or
close as determined by the
setting in Parameter 44. The
DN Flt parameters supersede the
Dn Idl parameters
Parameter Number
43
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB DN IdlValue
This parameter determines the
state that Output B assumes
when the network is idle and
Parameter 43 is set to “0”
0 = Open
1 = Close
Parameter Number
44
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0