Rockwell Automation 284 ArmorStart User Manual User Manual
Page 116
![background image](/manuals/577766/116/background.png)
4-26
Bulletin 283 Programmable Parameters
Zone #2 EPR
The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this value,
the zone connection will time out
and “Zone #2 Health” will report
1 = Not Healthy.
Parameter Number
87
Access Rule
GET/SET
Data Type
UNIT
Group
ZIP Parameters
Units
msec
MinimumValue
0
Maximum Value
65535
Default Value
75
Zone #3 EPR
The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this value,
the zone connection will time out
and “Zone #3 Health” will report
1 = Not Healthy.
Parameter Number
88
Access Rule
GET/SET
Data Type
UNIT
Group
ZIP Parameters
Units
msec
MinimumValue
0
Maximum Value
65535
Default Value
75
Zone #4 EPR
The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this value,
the zone connection will time out
and “Zone #4 Health” will report
1 = Not Healthy.
Parameter Number
89
Access Rule
GET/SET
Data Type
UNIT
Group
ZIP Parameters
Units
msec
MinimumValue
0
Maximum Value
65535
Default Value
75
Zone #1 Control
Zone 1 Control Word. Default Bit 0 and Bit 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages.
Parameter Number
90
Access Rule
GET/SET
Data Type
BYTE
Group
ZIP Parameters
Units
—
MinimumValue
0
Maximum Value
255
Default Value
3
Zone #2 Control
Zone 2 Control Word. Default Bit 0 and Bit 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages
Parameter Number
91
Access Rule
GET/SET
Data Type
BYTE
Group
ZIP Parameters
Units
—
MinimumValue
0
Maximum Value
225
Default Value
3