Rockwell Automation 284 ArmorStart User Manual User Manual
Page 202
6-28
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Motor OL Current
Set to the maximum allowable current. The drive fault on an F7 Motor Over load if
the value of this parameter is exceeded by 150% for 60 seconds.
Parameter Number
133
Related Parameter
155, 158, 161, 189, 190, 198,
214, 218
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
0.1 A
Minimum Value
0.0
Maximum Value
Drive rated amps x 2
Default Value
Based on Drive Rating
Minimum Freq
Sets the lowest frequency the drive will output continuously.
Parameter Number
134
Related Parameter
101, 102, 113, 135, 185, 186,
187, 210, 212
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400
Default Value
0.0
Maximum Freq
Sets the Highest frequency the drive will output continuously.
Parameter Number
135
Related Parameter
101, 102, 113, 134, 135, 178,
185, 186, 187, 211, 213
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400
Default Value
60.0
Start Source
Sets the control scheme used to start the Bulletin 284 ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
Parameter Number
136
Related Parameters
112 and 137
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
—
Minimum Value
0
Maximum Value
5
Default Value
5
Stop drive before changing this parameter.
Stop drive before changing this parameter.