beautypg.com

Rockwell Automation 284 ArmorStart User Manual User Manual

Page 202

background image

6-28

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Motor OL Current
Set to the maximum allowable current. The drive fault on an F7 Motor Over load if
the value of this parameter is exceeded by 150% for 60 seconds.

Parameter Number

133

Related Parameter

155, 158, 161, 189, 190, 198,

214, 218

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps x 2

Default Value

Based on Drive Rating

Minimum Freq
Sets the lowest frequency the drive will output continuously.

Parameter Number

134

Related Parameter

101, 102, 113, 135, 185, 186,

187, 210, 212

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400

Default Value

0.0

Maximum Freq

Sets the Highest frequency the drive will output continuously.

Parameter Number

135

Related Parameter

101, 102, 113, 134, 135, 178,

185, 186, 187, 211, 213

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400

Default Value

60.0

Start Source

Sets the control scheme used to start the Bulletin 284 ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port

Parameter Number

136

Related Parameters

112 and 137

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

Minimum Value

0

Maximum Value

5

Default Value

5

Stop drive before changing this parameter.

Stop drive before changing this parameter.

This manual is related to the following products: