Rockwell Automation 284 ArmorStart User Manual User Manual
Page 356
![background image](/manuals/577766/356/background.png)
B-12
Bulletin 280/281 CIP Information
Instance 4 is the Predefined Group 2 Connection Set Change of State/
Cyclic I/O Message Connection. The following instance 4 attributes
are supported:
Table B.30 Connection Object Instance 4 Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0=nonexistant
1=configuring
3=established
4=timed out
2
Get
Instance Type
USINT
1=I/O Connection
3
Get
Transport Class Trigger
USINT
0x00 (Cyclic, unacknowledged)
0x03 (Cyclic, acknowledged)
0x10 (COS, unacknowledged)
0x13 (COS, acknowledged)
4
Get
Produced Connection ID
UINT
01101xxxxxx
xxxxxx=node
address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx=node
address
6
Get
Initial Comm Characteristics
USINT
0x02 (acknowledged)
0x0F (unacknowledged)
7
Get
Produced Connection Size
UINT
0 to 8
8
Get
Consumed Connection Size
UINT
0 to 8
9
Get/Set
Expected Packet Rate
UINT
in ms
12
Get
Watchdog Action
USINT
0=transition to timed out
1=auto delete
2=auto reset
13
Get
Produced Connection Path Length
UINT
8
14
Get
Produced Connection Path
21 04 00 25 (assy inst) 00 30 03
15
Get
Consumed Connection Path Length
UINT
8
16
Get/Set
Consumed Connection Path
21 04 00 25 (assy inst) 00 30 03