Rockwell Automation 284 ArmorStart User Manual User Manual
Page 357
Bulletin 280/281 CIP Information
B-13
Instances 5 through 7 are available group 3 explicit message
connections that are allocated through the UCMM. The following
attributes are supported:
Table B.31 Connection Object Instance 5-7 Attributes
Instances 8-11 are ZIP Consumers. The following instance attributes
will be supported:
Table B.32 Connection Object Instances 8-11 Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0=nonexistant
1=configuring
3=established
4=timed out
2
Get
Instance Type
USINT
0=Explicit
Message
3
Get
Transport Class Trigger
USINT
0x83 — Server, Transport Class 3
4
Get
Produced Connection ID
UINT
Depends on message group and Message ID
5
Get
Consumed Connection ID
UINT
Depends on message group and Message ID
6
Get
Initial Comm Characteristics
USINT
0x33 (Group 3)
7
Get
Produced Connection Size
UINT
0
8
Get
Consumed Connection Size
UINT
0XFFFF
9
Get/Set
Expected Packet Rate
UINT
in ms
12
Get
Watchdog Action
USINT
01 = auto delete
03 = deferred delete
13
Get
Produced Connection Path Length
UINT
0
14
Get
Produced Connection Path
Empty
15
Get
Consumed Connection Path Length
UINT
0
16
Get
Consumed Connection Path
Empty
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0=nonexistant
1=configuring
3=established
2
Get
Instance Type
USINT
1=I/O Connection
3
Get
Transport Class Trigger
USINT
0x20 (COS, unacknowledged)
4
Get
Produced Connection ID
UINT
FFFF (not producing data)
5
Get
Consumed Connection ID
UINT
01101xxxxxx
xxxxxx=node address
6
Get
Initial Comm Characteristics
USINT
0xF0 (unacknowledged)
7
Get
Produced Connection Size
UINT
0
8
Get
Consumed Connection Size
UINT
8
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get
Watchdog Action
USINT
2=auto reset
13
Get
Produced Connection Path Length
UINT
0
14
Get
Produced Connection Path
0
15
Get
Consumed Connection Path Length
UINT
8
16
Get
Consumed Connection Path
21 0E 03 25 01 00 30 02