Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
6-39
Jog Accel/Decel
Sets the acceleration and deceleration time when a jog command is issued.
Parameter Number
179
Related Parameters
178, 151, 152, 153, 154
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.1
Maximum Value
600.0
Default Value
10.0
DC Brake Time
Sets the length of time that DC brake current is injected into the motor. Refer to
Parameter 181 DC Brake Level.
Parameter Number
180
Related Parameters
137, 181
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.0
Maximum Value
99.9
(Setting of 99.9 = Continuous)
Default Value
0.0
DC Brake Level
Defines the maximum DC brake current, in amps, applied to the motor when
Parameter 137 (Stop Mode) is set to either Ramp or DC Brake.
Parameter Number
181
Related Parameters
137, 180
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 A
Minimum Value
0.0
Maximum Value
Drive rated amps X 1.8
Default Value
Drive rated amps X 0.05
ATTENTION
!
• If a hazard of injury due to movement of equipment or
material exists, an auxiliary mechanical braking device must
be used.
• This feature should not be used with synchronous or
permanent magnet motors. Motors may be demagnetized
during braking.