Rockwell Automation 284 ArmorStart User Manual User Manual
Page 394
![background image](/manuals/577766/394/background.png)
C-22
Bulletin 283 CIP Information
The following common services are implemented for the Parameter
Object:
Table C.43 Parameter Object Common Services
Parameter Group Object — CLASS
CODE 0x0010
The following class attributes are supported for the Parameter Object:
Table C.44 Parameter Group Object Class Attributes
All Bulletin 283 Motor Starters have the following instances of the
parameter group object:
•
Instance 1 = DeviceLogix Parameters
•
Instance 2 = DeviceNet Parameters
•
Instance 3 = Starter Protection Parameters
•
Instance 4 = User I/O Parameters
•
Instance 5 = Miscellaneous Setup Parameters
•
Instance 6 = ZIP Parameters
•
Instance 7 = SoftStart Display
•
Instance 8 = Soft Start Setup
The following instance attributes are supported for all parameter
group instances:
Table C.45 Parameter Group Object Instance Attributes
The following common services are implemented for the Parameter
Group Object:
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x01
No
Yes
Get_Attributes_All
Attribute ID
Access Rule
Name
Data Type
1
Get
Revision
UINT
2
Get
Max Instance
UINT
Attribute ID
Access Rule
Name
Data Type
1
Get
Group Name String
SHORT_STRING
2
Get
Number of Members
UINT
3
Get
1
st
Parameter
UINT
4
Get
2
nd
Parameter
UINT
n
Get
Nth Parameter
UINT