Power receptacles, Specifications – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 338
A-18
Specifications
Power Receptacles
Specifications
Trunk Tee: 25 A
A
Female
Male
1 Black
3
Red
2 Green/Yellow Extended PIN
4
White
Reducing Tees
Trunk: 25 A
Drop: 15 A
B
Female
Male
Female
1 Black
3
Red
2 Green/Yellow Extended PIN
4
White
1 Black
2 Green/Yellow Extended PIN
3 Red
4 White
Reducer
Trunk: 25 A
Drop: 15 A
C
Male
Female
1 Black
3
Red
2 Green/Yellow Extended PIN
4
White
1 Black
2 Green/Yellow Extended PIN
3 Red
4 White
Certifications
UL
Standards Compliance
UL 2237
Mechanical
Insert
Black PVC
Receptacle Shell Material
Black Anodized Aluminum (female) and Zinc DieCast, Black
E-Coat (male), or 316 Stainless Steel
Electrical
Contacts
Copper Alloy with Gold over Nickel Plating (Trunk), Brass
with Gold over Nickel Plating (Drop)
Cable Rating
600V AC/DC
Assembly Rating
4 pin - 16 AWG, 600V @ 10 A
4 pin - 14 AWG, 600V @ 15 A
4 pin - 10 AWG, 600V @ 25 A
Symmetrical Amps RMS Fault: 65 kA when used with Class
CC, T, or J type fuses
Environmental
Enclosure Type Rating
IP67, NEMA 4; IP69K 1200 psi washdown