Rockwell Automation 284 ArmorStart User Manual User Manual
Page 299
Troubleshooting
14-5
Table 14.3 Fault LED indications for Bulletin 283 ArmorStart Distributed
Motor Controllers
➊
Not available on the Bulletin 283A.
Blink
Pattern
Definitions
Possible Causes or Remedies
1
Short Circuit
The motor circuit protector has tripped, or the internal wiring protection algorithm has detected an unsafe
current range. Try to reset the protector if tripped. If the condition continues, check the power wiring. This
fault cannot be disabled.
2
Overload trip
The load has drawn excessive current and based on the trip class selected, the device has tripped. Verify
that the load is operating correctly and the ArmorStart is properly set-up. This fault cannot be disabled.
3
Phase Loss
The ArmorStart has detected a missing phase. Verify that three phase voltage is present at the line side
connections. This fault can be disabled and is disabled by default.
4
Shorted SCR
Prior to every start, the unit will check all SCRs for shorts and unit load connections to the motor. If there is
a shorted SCR in the SMC-3 and/or open load, the start will be aborted and a shorted SCR/open load fault
will be indicated. This prevents damage from phase imbalance. This fault cannot be disabled.
5
Phase Rotation
When enabled, 3-phase input power will be verified before starting. If input power phasing is detected to
be incorrect, the start will be aborted and a fault indicated. This fault can be disabled and is disabled by
default.
6
Control Power
The ArmorStart has detected a loss of the control power voltage or blown control power fuse. Check control
voltage, wiring, and proper polarity. Replace control voltage fuse if necessary. This fault can be disabled
and is disabled by default.
7
I/O Fault
This error indicates a shorted sensor, shorted input device, wiring input mistakes, or a blown output fuse. If
this fault occurs, the offending problem should be isolated or removed prior to restarting the system. This
fault can be disabled and is disabled by default.
8
Over Temperature
Indicates an over temperature condition. This fault cannot be disabled.
9
Phase Imbalance
The ArmorStart has detected a voltage imbalance. Check the power system and correct if necessary. This
fault cannot be disabled.
10 ➊
DNet Power Loss
DeviceNet™ power has been lost or has dropped below the 12V threshold. Check the state of the network
power supply and look for DeviceNet media problems. This fault can be disabled and is disabled by default.
11
Internal Communication
This fault occurs when communication between the main board and the SMC-3 is lost. This fault cannot be
disabled.
12
Heatsink Over
temperature/JAM
This fault indicates either an over temperature fault or a JAM fault. The heatsink is monitored by
thermistors and the SCR temperature is tracked by an algorithm. When a maximum temperature is reached
by either, the microcomputer switches off the SMC and indicates a fault code of 12. A fault code of 12
could also indicate a JAM fault. This fault cannot be disabled.
13
EEPROM Fault
This is a major fault, which renders the ArmorStart inoperable. Possible causes of this fault are transients
induced during EEprom storage routines. If the fault was, initiated by a transient, power cycling should
clear the problem otherwise replacement of the ArmorStart may be required. This fault cannot be disabled.
14
Hardware Fault
This fault indicates that a serious hardware problem exists. Check for a base/stater module mismatch or a
blown source brake fuse. If no mismatch exists or the source brake fuse is OK, the ArmorStart may need to
be replaced. (Hdw Flt is the factory-enabled default setting.) This fault cannot be disabled.
16
Miscellaneous Fault
This fault cannot be disabled.