Rockwell Automation 284 ArmorStart User Manual User Manual
Page 397

Bulletin 283 CIP Information
C-25
Control Supervisor Object -CLASS
CODE 0x0029
No class attributes will be supported.
A single instance (instance 1) of the Control Supervisor Object will
be supported.
Attribute ID
Access
Rule
Name
Data Type
Value
3
Get/Set
Run 1
BOOL
Run1 output also map to DOP
instance 1.
7
Get
Running 1
BOOL
9
Get
Ready
BOOL
10
Get
Tripped
BOOL
12
Get/Set
Fault Reset
BOOL
0->1 = Trip Reset
100
Get/Set
Keypad Mode
BOOL
0=Maintained; 1=Momentary
101
Get/Set
Keypad Disable
BOOL
0=Not Disabled; 1=Disabled
115
Get
Warning Status
WORD
Bits 0-1 = reserved
Bit 2 = PL Warning (283 Only)
Bit 3 = reserved
Bit 4 = PR Warning (283 only)
Bit 5 = CP Warning
Bit 6 = IO Warning
Bit 7 = reserved
Bit 8 = PI Warning (283 only)
Bit 9 = DN Warning
Bits 10-12 = reserved
Bit 13 = HW Warning
Bits 14-15 = reserved
124
Get/Set
Trip Enable
WORD
Bit enumerated trip enable word
130
Get/Set
Trip Reset Mode
BOOL
0=manual
1=auto
131
Get/Set
Trip Reset Level
USINT
0 – 100%; default = 75
151
Get
Base Enclosure
WORD
Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2-15 reserved
152
Get
Base Options
WORD
Bit 0 = Output Fuse
Bit 1 = Safety Monitor
Bit 2 = CP Fuse Detect
Bits 3-7 = Reserved
Bit 8 = 10A Base
Bit 9 = 25A Base
Bit 10-15 = Reserved
153
Get
Wiring Options
WORD
Bit 0 = Conduit
Bit 1 = Round Media
Bits 2-15 = Reserved
154
Get
Starter Enclosure
WORD
Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2-15 reserved
155
Get
Starter Options
WORD
Bit 0 = Full Keypad
Bit 1 = Safety Monitor
Bit 2 = Source Brake
Bit 3-15 = Reserved
156
Get
Last PR Trip
UINT
See Parameter 61 for definitions