Rockwell Automation 284 ArmorStart User Manual User Manual
Page 348
![background image](/manuals/577766/348/background.png)
B-4
Bulletin 280/281 CIP Information
DeviceNet Object — CLASS CODE
0x0003
The following class attributes are supported for the DeviceNet Object:
Table B.7 DeviceNet Object Class Attributes
A single instance (instance 1) of the DeviceNet Object is supported.
The following instance attributes are supported.
Table B.8 DeviceNet Object Instance Attributes
The following services are implemented for the DeviceNet Object:
Table B.9 DeviceNet Object Common Services
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2
Attribute ID Access Rule
Name
Data Type
Value
1
Get/Set
Node Address
USINT
0 - 63
2 Get/Set
Baud
Rate
USINT
0=125K
1=250K
2=500K
3 = 1M ➊
5
Get
Allocation Info
Allocation Choice
Master Node Addr
Structure of:
BYTE
USINT
Allocation_byte*
0…63 = address
255 = unallocated
8
Get
MAC ID Switch Value
BOOL
0-63
➊
1M baud is only available on the Bulletin 280A/281A.
*Allocation_byte
Bit 0
Explicit messaging
Bit 1
Polled I/O
Bit 4
COS I/O
Bit 5
Cyclic I/O
Bit 6
Acknowledge Suppression
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x4B
No
Yes
Allocate_Master/Slave
_Connection_Set
0x4C
No
Yes
Release_Master/Slave
_Connection_Set