Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
6-61
EM Brk Off Delay
Sets the time the drive will remain at minimum frequency before ramping to the
commanded frequency and energizing the brake coil relay when Parameter 137 (Stop
Mode) is set to option 8 or 9.
Parameter Number
260
Related Parameters
137
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
0.01 sec
Minimum Value
0.01 sec
Maximum Value
10 sec
Default Value
0.0 sec
EM Brk On Delay
Sets the time the drive will remain at minimum frequency before stopping and de-
energizing the brake coil relay when Parameter 137 (Stop Mode) is set to option 8 or
9.
Parameter Number
261
Related Parameters
137
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
0.01 sec
Minimum Value
0.01 sec
Maximum Value
10.00 sec
Default Value
0.0 sec
MOP Reset Sel
Sets the drive to save the current MOP Reference command.
0 = Zero MOP Ref
This option clamps Parameter 169 (Internal Freq) at 0.0 Hz when drive is not running.
1 = Save MOP Ref (Default)
Reference is saved in Parameter 169 (Internal Freq).
Parameter Number
262
Related Parameters
169
Access Rule
Get/Set
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Frequency
Time
Minimum Freq
260 [EM Brk Off Delay]
261 [EM Brk On Delay]
Stop
Commanded
Start
Commanded
EM Brk
De-Energized (On)
Drive Stops
EM Brk
Energized (Off)
Ramp Accel
Ramp Decel